The DN-EM Energy Meter / BTU Meter is an economical energy flow meter intended for applications in energy transfer and heating/ cooling systems where energy use requires measurement.
In heat exchange loops the DN-EM internally calculates the energy gained or lost by the heat exchanger. The energy is calculated based on the the mass volume rate and the difference in temperature between the supply and return lines. The volume of liquid is measured by means of a pulse generating vortex flow meter. A RTD sensor built into the flow meter (T1) measures temperature at the meter and the remote temperature (T2) is measured by means of a precision RTD sensor mounted in a pipe tee.
A scaled pulse output is provided and can be configured to report volume flow rate, mass flow rate or energy total. Modbus 485 communications provides an interface with a building automation or monitoring system.
The unit contains non-volatile memory that records, mass flow and energy, and is updated every ten minutes. However, when flow, mass or energy totals are read, the reported values are true current values; the last stored value is added to the current accumulated value when the applicable register is read.
The default medium for the DN-EM is water. Other media consisting of water and a certain percentage of glycol up to 60% can be field configured.
| Model | Pipe Size | Full Scale Range (Gal/min) | Full Scale Range (l/min) | Flow Pulse Output Configuration (Pulses/Gallon) | Flow Formula (Q=Flow in GPM) | Max. Pressure Drop (PSI) |
| DN-EM8 | 1/4" | 0.25 to 4.00 | 0.9 to 15.0 | 7200 | Q= 0.00833xFreq. | 2.9 |
| DN-EM10 | 3/8" | 0.50 to 8.00 | 1.8 to 32.0 | 3600 | Q= 0.01667xFreq. | |
| DN-EM15 | 1/2” | 0.90 to 13.20 | 3.5 to 50.0 | 2000 | Q= 0.06xFreq. | |
| DN-EM20 | 3/4” | 1.30 to 22.50 | 5.0 to 85.0 | 1200 | Q= 0.1xFreq. |
Medium: Suitable for water & water glycol based heat exchange systems and other liquids compatible with the materials of construction (consult factory). For media with viscosity greater than 2 millipascal seconds (2 centipoise), higher flow rates are required to form vortices raising the minimum measurable flow rate value. Flow ranges: From 0.25 to 22.5 GPM, See Table 1 Temperature measurement: 3-wire,1000 Ohm RTD 1 RTD imbedded in flow sensor 1 RTD packaged in a 1/4" x 2.5" stainless steel sheath with 1/2" NPT brass adjustable compression fitting for mounting in a 1/2" or 3/4" pipe Tee; supplied connected to energy monitor with 10 ft of 3-wire RTD cable. Pipe Tee is an ordering option, see Table 11. Temperature: Ambient: 5° to 185°F (15° to +85°C) In storage: -22° to 185°F (-30° to +85°C) Max. pressures and liquid temperature: See table 2
| PSI | Bar | °F | °C | Duration |
| 174 | 12 | 104 | 40 | Lifetime |
| 100 | 6.89 | 200 | 93.3 | Lifetime |
| 87 | 6 | 212 | 100 | Lifetime |
| 58 | 4 | 257 | 125 | 600 hours |
| 58 | 4 | 284 | 140 | 2 hours |
Max. test pressure: 261 psi/18 bar at 104°F/40°C Loss of pressure / cavitation: A minimum inlet pressure of 10.2 psi (0.7 bars) is required to avoid cavitation issues at maximum flow. Wetted materials: Flow sensor and bluff: ASTM- PPA, Polyphthalamide ISO-PA6T/6I, Grivory 40%GF Sensor vane: ETFE Sealing material: EPDM Flow Accuracy: Up to 50% fs: ≤ 1% fs From 50% fs: ≤ 2% of measured value Temperature measurement accuracy: Reported supply & return temperatures are per PT1000, DIN EN 60751 Class B. Temperature difference used in energy calculation is product of matched pair RTDs calibrated at factory to report temperature difference to ±(0.1 + 0.002*T) Degs C. Operating Differential Temperature Range: 3°C to 91°C (5.4 to 164°F), consult factory for other. System accuracy: EN1434-1, Class 2 & 3 (see Table 3) Protection class: NEMA 4X (IP65) Mounting position: Flow direction is identified by an arrow on flowmeter body. Otherwise the flowmeter mounting orientation is universal. Units of Measurement: Factory set or Field programmable Flow Rate: Gals/Min, Liters/Min Mass Flow: Lbs/Min, Kgs/Min Energy Rate: BTU/Min, kBTU/Min, kBTU/Hr, KW Total Flow: Gals, Liters, Cubic Meters Total Energy: kBTU, KW-HRS Temperature: °F, °C Output Update Rate: 2 seconds Power: 12 to 30 VDC Current Consumption: < 10 mA Pulse Output: Can be factory set or field configured to report volume flow rate, mass flow rate or energy total. Output is either an optically isolated NPN transistor with maximum sinking capability to 50 mA from a voltage source of no more than 48 VDC or a voltage output (power supply voltage). Pulse duration is 2 ms when reporting flow rate and 10 ms when reporting energy total (consult factory for different pulse duration) Security: Holographic tamper evident label seal with unique serial number provided for electrical enclosure cover. Optional hour meter mounted in enclosure cover available to monitor power. Energy Measurement: T1 RTD is located in the flow sensor T2 Remote RTD is installed in a pipe tee Heating and cooling energy are both measured and totaled in separate registers in model DN-EM. The values can be interrogated via the Modbus Master. 1) Heating Mode: T1>T2 2) Cooling Mode: T2>T1 Depending on factory or field setup, the energy total pulse output functions in the absolute mode, indifferent as to whether in the heating-or-cooling mode,heating-only mode or cooling-only mode. Modbus Operability: Baud Rate: 9600 (default) or 19.2 KB/S Parity: Selectable, None (default), Even, Odd Slave Id: 01-255 (default is 01) Function Codes: 03, 05 & 06 are supported Exception Codes: 01, 02 & 03 are supported Data types: Word, Double Data is sent "Big Endian", i.e. most significant byte first Flow and energy data updated every 2 seconds. Turn around time is less than 2 seconds. Since the data is updated every 2 seconds, reading data at intervals greater than the update time will ensure that current values will always be fresh. Commissioning: The DN-EM requires no special software to set the desired communication parameters. It can be done at the factory or from the User's Modbus Master over the RS-485 network. Stand alone commissioning can be done via PC serial port (model 43-119, RS-485 converter required). A 600 Ohm bus termination resistor can be jumper selected on the pcb. Download commissioning software HERE. Wiring Connection: 10 ft shielded 3-conductor plenum cable for RS-485 10 ft shielded 4-conductor plenum cable for power & pulse output. Liquidtight 1/2" non-metallic conduit connector supplied for cable entry to enclosure Pipe Connections: 304 Stainless Steel threaded adapters or brass solder adapters, see tables 7 & 8.
| Flow Percent F.S. | 10 | 20 | 30 | 40 | 50 | 60 | 70 | 80 | 90 | 100 | |
| Delta T ¼C | Delta T ¼F | ||||||||||
| 3.0 | 5.4 | 14.4% | 9.6% | ||||||||
| 3.9 | 7.0 | 13.4% | 8.5% | ||||||||
| 5.1 | 9.1 | 12.5% | 7.7% | ||||||||
| 6.6 | 11.9 | 11.9% | 7.0% | ||||||||
| 8.6 | 15.4 | 11.4% | 6.5% | ||||||||
| 11.1 | 20.0 | 11.0% | 6.1% | ||||||||
| 14.5 | 26.1 | 10.7% | 5.9% | ||||||||
| 18.8 | 33.9 | 10.5% | 5.6% | ||||||||
| 24.5 | 44.0 | 10.3% | 5.5% | ||||||||
| 31.8 | 57.3 | 10.2% | 5.3% | ||||||||
| 41.4 | 74.4 | 10.1% | 5.2% | ||||||||
| 53.8 | 96.8 | 10.0% | 5.1% | ||||||||
| 69.9 | 125.8 | 10.0% | 5.1% | ||||||||
| 90.9 | 163.6 | 9.9% | 5.0% | ||||||||
| Class 2 & 3 | Class 2 | ||||||||||
A b o u t E N 1 4 3 4 - 1 M a x . P e r m i s s a b l e E r r o r s o f C o m p l e t e H e a t M e t e r s C l a s s 2 : E = ± ( 3 + 4"ΔΘ