PRODUCT SPECIFICATIONS > INSTRUMENTATION

Clark Solutions

EX 100/200 Series Electromagnetic Liquid
Flow Transmitters

Flow rates from 2.1 GPM to 25000 GPM,
3" to 48" Pipe Sizes

DESCRIPTION

The complete lack of moving parts of this insertion flow sensor is the source of its reliability. There is no rotor to stop turning in dirty water and there are no bearings to wear out. A rapidly reversing magnetic field is produced in the lower housing, and as the fluid moves through this field a voltage is generated. This tiny voltage is measured and translated into a frequency signal which is proportional to flow rate. This square wave signal can be sent directly to a PLC or other control, or can be converted using any of the associated family of indicators and converters.

A modular system of electronics can be attached directly to the flow sensor or remotely mounted. The FT420 provides full indication of rate and total, plus 4- 20 mA output. The AO55 provides a 4-20 mA output, and the FS30 can be used as a precise setpoint flow switch.

The installation fitting of the EX sensor is standard male NPT, and can be directly threaded into ordinary saddles or threaded weld fittings. The EX115 and 215 include an isolation valve, allowing hot-tap installation or installation and removal under pressure. The standard isolation valve is Bronze, but a 316 Stainless Steel valve is available as an option if needed.

SPECIFICATIONS

Power: 12 - 24 Vdc, 250 mA
Flow Range: 0.2 to 20 ft/sec (.06 - 6.09 m/sec)
Fitting Size: EX101, 201 = 1½" MNPT; EX115, 215 = 2" MNPT
Installation Pipe Sizes: EX101/EX115, 3" to 10" pipe; EX201/EX215,
   10" to 48"
Temperature: Ambient, 0° to 180°F (-17 - 82°C); Fluid,
   32° to 212°F (0° - 100°C)
Pressure: 200 psi (13.8 bar)
Minimum Conductivity: 20 microsiemens/cm
Mechanical Materials: 316 SS or Brass
Electrodes: Carbon Graphite
Electrode plate: PVDF
Housing: Cast powder-coated aluminum
O-rings: EPDM
Calibration Accuracy: 1% of full scale
Output: Square wave pulse, opto-isolated, 500 Hz @ 20 ft/sec is standard.
   4-20 mA, rate and total indicator and alarm output are optional.
Bi-directional: Direction output, opto-isolated
Empty Pipe Detection Software: defaults to zero flow.

FEATURES

Features

Features Magmeter Insertion Depth
The meter only extends approximately 1/8th of diameter into the pipe, minimizing the potential for clogging due to debris.

 

Features

Flow Range (GPM)
Pipe Size Min. Flow Max. Flow
2 2.1 209
3 4.6 461
4 7.9 794
6 18 1,800
8 31.2 3,120
10 49.2 4,920
12 70 6,980
16 110 11,020
24 251 25,060

 

Pipe K Factors (Pulses per Gallon) for Various Pipe Sizes

 

2" 3" 4" 6" 8" 10" 12" 14" 16" 18" 20" 22" 24" 30" 36" 42" 48"
Sch. 40 PVC/Steel 143.4 65.01 37.80 16.66 9.62 6.10 4.30 3.56 2.72 2.152 1.731 - 1.197 - 0.515 - -
Sch. 80 PVC/Steel 163.0 72.86 41.86 18.46 10.54 6.70 4.74 3.92 2.99 2.357 1.904 1.571 1.318 0.722 0.497 - -
Stainless Steel (10S) 131.7 57.66 33.76 16.20 8.83 5.64 3.99 3.30 2.51 1.973 1.601 1.318 1.110 0.710 - - -
Stainless Steel (40S) 143.4 65.01 37.80 16.66 9.62 6.10 4.19 3.49 2.63 2.059 1.654 1.357 1.134 0.716 0.493 0.360 0.263
Type L Copper Tubing 155.5 70.65 40.18 17.94 10.27 6.61 4.58 - - - - - - - - - -
Type. K Copper Tubing 159.7 72.51 41.19 18.59 10.66 6.86 4.79 - - - - - - - - - -
Copper Pipe 144.3 65.35 38.80 16.33 9.58 6.13 - - - - - - - - - - -
Class 52 Duct. Iron - - 34.41 15.54 8.71 5.65 3.95 2.91 2.22 1.756 1.422 - 0.987 0.635 - - -

OPTIONAL OUTPUT MODULES

These modules mount directly on the EX series electrical enclosure or remote mount on
a wall or in a panel

FT420: Indicating transmitter features rate and total display and 4-20 mA output. It also provides scaled pulse output for solenoid driven pump pacing, a pulse pass through for use with a PLC, and a programmable flow rate setpoint.

Power: 4-20 mA Loop Powered, 12-32 VDC
Rate Display: 6-digit autorange, ½" character height.
Pulse Output: 0.1 sec.open collector pulse (scaled);
   high or low alarm; sensor pulse (unscaled)
Input: pulse frequency, +5 VDC K
Factor Range: 0.050-999999.9
Pulse Output Range: 0.1-200,000 units/pulse
Flow Alarm Output Range: 0.1-999999.99
Enclosure: NEMA 4X

A055: 4-20 mA output module is easily scaled using rotary switches to enter the desired top end of range.

Power: 12-36 VDC
Temperature: 32°-130°F (0° to 55°C)
Input: open-collector, solid-state
Min Frequency: 10 Hz (@20 mA)
Max. Frequency: 999.9 Hz
Output: Proportional 4-20 mA
Frequency Setting: 4 Rotary DIP switches
Input Averaging: 2-16 seconds, switch selectable
Response Time: 2-60 seconds 90% full scale.

FS30: Converts mag flow sensor to a flow switch. Setting is easy using rotary switches inside the housing. An indicator shows switch status.

Power: 12-36 VDC
Flow Sensor Power: 5VDC, 20 mA
Temperature: 32°-120°F (0° to 48.9°C)
Output: Form C relay, 10A @ 120Vac or 28 VDC max
Setting Range: 1-999 Hz
Accuracy: 1%
Hysteresis: Adjustable 1-10%
Modes: High (close on rise), Low (close on fall)
Switch Response (after 90% change): 2 sec. rise, 3 sec. fall
Indicator: Power on (green), switch (red)
Output: Open Collector transistor, 100 mS duration.

FT420- Meter Mount

FT420



A055 Meter Mount

A055


FS30 MOdule

FS30

ORDERING INFORMATION

EXAMPLE: EX115-S-A055

PLEASE CALL 1-800-253-2497 TO ORDER THESE ITEMS
Model Material
EX101 B = Brass
EX201 S = 316 SS
EX115  
EX215
 
 
Options
- = Pulse Output (standard)
FT420M = FT420 (mount in transmitter enclosure)
*FT420W = FT420 (remote wall mounting)
A055M = A055 (mount in transmitter enclosure)
*A055W = A055 (remote wall mounting)
FS30M = FS30 (mount in transmitter enclosure)
*FS30W = FS30 (remote wall mounting)
*Supplied with brackets for wall mounting