Clark Solutions

CFS400 Series Shuttle Type Flow Switch

General Purpose 90° Flow Path, Liquid Flow Set Points from 0.75 GPM to 14 GPM

DESCRIPTION

CFS400 series provide accurate flow detection in water and oil with 1% repeatability. They are available in factory preset or field adjustable versions.

Flow settings on the adjustable version can be easily changed without disassembly. A shuttle by-pass vane inside the housing is controlled externally using an ordinary flat-blade screwdriver.

These switches are ruggedly constructed of non-corrosive materials and resist shock and vibration. They are suitable for triggering alarms on interlocking shutdown circuitry when flow rate is improper to protect bearings, gears and cooling systems.

Click here for information on our other flow switches.

SPECIFICATIONS

Wetted Materials:
     Housing: Bronze
     Shuttle: Delrin®
     Spring: 316 Stainless Steel
     O-Ring: Viton®
     Other Wetted Parts: Ceramic
Pressure Rating:
     Max. Operating: 400 PSI @ 100°F (+37.8°C)
     Proof: 800 PSI @ 100°F (+37.8°C)
Operating Temperature: -20°F to +180°F
     (-29°C to +82.2°C)
Repeatability: 1% Maximum Deviation
Set Point Accuracy: ±10%
Set Point Differential: 15% Maximum
Switch: SPDT, 20 VA
Switch Rating, Maximum Resistive Load
VA Volts Amps AC Amps DC
20 0-30 0.4 0.3
120 0.17 0.13
240 0.08 0.06
Inlet/Outlet Ports: 3/4" NPT Electrical Termination: No. 22 AWG, 24" to 26" Polymeric leads Hazardous Rating: CFS400 Series Flow Switches are U.L. Approved for Class I, Division 2, Groups A, B, C, D hazardous areas.
Shuttle Type Flow Switch Typical Pressure Drop ORDERING INFORMATION
FOR YOUR CONVENIENCE, THESE ITEMS ARE AVAILABLE ONLINE
OR PLEASE CALL 1-800-253-2497 TO ORDER THESE ITEMS
Field Adjustable Setpoint CFS400
NPT Flow Setting GPM Part Number
3/4" 0.75-4.0 C26600
2.0-8.0 C26601
7.0-14.0 C26602
FOR YOUR CONVENIENCE, THESE ITEMS ARE AVAILABLE ONLINE
OR PLEASE CALL 1-800-253-2497 TO ORDER THESE ITEMS
Fixed Setpoint CFS400
NPT Flow Setting GPM Part Number
3/4" 0.75 C26440
1.5 C26441
2.0 C26442
2.5 C26443
5.0 C26444
7.5 C26445
10.0 C26446

Qty:

Show Discount Schedule

Notes: Flow settings for Fixed Version are calibrated using water at +70°F on increasing flow, with units in a vertical position (lead wires up). Temperature changes will slightly affect the flow settings listed. Adjustable units that are set to customer specifications are subject to factory test stand accuracy. Use of 150 micron filtration is recommended. Minimum 5 PSI line pressure required.

For assistance call 978-568-3400