INSTRUMENTATION > FLOW > CS-EM BTU/Energy Monitor
Clark Sonic logo

CS-EM BTU/Energy Monitor — Available Spring 2012

Energy Monitoring of Heating or Cooling Systems, 3/4” to 10” Pipe

DESCRIPTION

The CS-EM is an economical energy flow monitor intended for applications in energy transfer and heating/cooling systems where energy use requires measurement.

In heat exchange loops the CS-EM internally calculates the energy gained or lost by the heat exchanger. The energy is calculated based on the the mass volume of liquid passing through the system and the difference in temperature between the supply and return lines. The volume of liquid is measured by means of a pulse generating Clark ultrasonic flow transmitter. An RTD sensor built into the flowmeter (T1) measures temperature at the meter and the remote temperature (T2) is measured by means of a precision RTD sensor mounted in the return pipe.

A scaled pulse output is provided and can be configured to report volume flow rate, mass flow rate or energy total. Modbus 485 communications provides an interface with a building automation or monitoring system.

The unit contains non-volatile memory that records flow and energy, and is updated every ten minutes. However, when flow, mass or energy totals are read, the reported values are true current values; the last stored value is added to the current accumulated value when the applicable register is read.

The default medium for the CS-EM is water. Other media consisting of water and a certain percentage of glycol up to 30% can be field configured.

APPLICATIONS

  • HEATING ONLY APPLICATION
  • COOLING ONLY APPLICATION
  • HEAT RECOVERY APPLICATIONS
  • CONDENSATE RECOVERY APPLICATIONS
  • EFFICIENCY MEASURING/VERIFICATION
  • SOLAR AND GEOTHERMAL SYSTEMS

SPECIFICATIONS

TEMPERATURE MEASUREMENT

RTD integral to Flow Transmitter: 
   Sensor: 100 Ohm Platinum RTD Element ( Alpha= 0.00385)
    Accuracy: ±0.06% at 0°C
Remote RTD Assembly:  Clark Spring-Loaded RTD Thermowell Assemblies with General Purpose 
	Aluminum Connection Heads are designed for use with, and supplied with, Clark 316 SS thermowells. 
	This design allows 1/4" spring compression to ensure positive contact with the bottom of the thermowell.
Sensor: 100 Ohm Platinum RTD Element ( Alpha= 0.00385)
Accuracy: ±0.06% at 0°C
Sheath material & Diameter: 316 SS, 1/4" dia.
Element Connection: 3 wire, screw terminal
Connection to Energy Monitor: 10 ft connecting RTD cable supplied with each model. 
	Cable installed at monitor end via water tight strain relief fitting and electrical connector.
Head Mounting Fittings: 316 SS, 1/2" x 1/2" NPT hex nipple, 1" length
Head & Sheath Termination: Aluminum screw cover head, 3/4" NPT conduit connection
Sizes: See model & dimension chart

THERMOWELL

Material: 316L SS
Pipe Conection: 3/4" NPT
Dimensions: See Table 1 below

Table 1

Remote RTD Model & Thermowell Dimension Chart
Model For Pipe Sizes See Figure S U
19-027 3/4", 1", 1-1/2", & 2" 1 - -
19-028 3" & 4" 2 4" 2-1/2"
19-029 6" & 8" 2 6" 4-1/2"
19-030 10" 2 9" 7-1/2"
Figure 1
Figure 2

FLOW TRANSMITTER WITH RTD SENSOR & INTEGRATED ELECTRONICS FOR ENERGY CALCULATIONS

DESCRIPTION

Clark Sonic ultrasonic flow transmitters are ideal for measurement of flow rates of acoustically conductive liquids including most clean liquids and many liquids with entrained solids. They are ideal for monitoring flow rate and temperature in heat exchange applications. When used in energy measurement applications the transmitters are typically supplied with a built-in platinum 100 Ohm RTD temperature sensor to monitor the process temperature.

Main advantages include excellent long term stability, no pressure drop, broad fluid compatibility, high accuracy and low cost. Also, there are no moving parts.

At the heart of the transmitter is a proprietary mixed signal ASIC which allows sophisticated timing, control and transducer drive circuitry to be combined on a single integrated circuit

The ASIC uses a special algorithm that is an improvement upon the standard single-path measurement technique. Using the “sing around” method, the ultrasonic transducer alternates between transmitting and receiving to measure differences in flight time between upstream and downstream transmissions. A sound pulse is transmitted from an upstream transducer towards a downstream transducer like a traditional time-of-flight measurement. However, the received sound pulse then triggers a second downstream  transmission, that then triggers a third and so on for a specific number of cycles. This process is repeated in the upstream direction.

Because it takes an average flight time over multiple cycles to compute the difference in flight times, the approach yields a significant improvement in timing accuracy when compared with the time-of -flight difference of a single sound pulse in each direction. This algorithm, combined with the pico-second timing resolution of the ASIC, provides the precise time measurement capability necessary for compact, small diameter ultrasonic meters.

The output of the transmitter is unaffected by changes in fluid temperature, density and viscosity as the flow calculation is independent of the speed of sound.

SPECIFICATIONS
GENERAL

Flow Range: Bi-directional, per "Standard Models" table
Accuracy: ±0.75% of full scale
Operating Temperature: -40 to 190°F (-40 to 87.8°C)
Response Time: User Selectable, 2 or 10 seconds
Viscosity Range: 0.2 to 150 cSt (0.2 to 150 mPas)
Liquid Density: 30.6 to 74.9 lb/cu.ft. (490 to 1200 kg/m3)
Max. Working Pressure:
	¾" to 2":250 PSI (17.2 bars)
	3" to 10": Per ASME 150 flange specification
Pipe Sizes: 3/4", 1", 1 1/2", 2", 3", 4", 6", 8", 10"
Pipe Connections:
See Model Tables 2 & 3
	Sizes 3/4" to 2"- Female NPT, BSP
	Size 3" to 10": ASME 150 Flange
Electrical Enclosure: Integral to Body casting with gasketed cover; One 1/2" NPT conduit connection
	and one M16 x 1.5 connection (used for remote RTD)
Enclosure Rating: NEMA 4 (IP 65)
Power Supply Voltage: 18 to 36 VDC

WETTED MATERIALS

Ultrasonic Transducers: ULTEM® Encapsulated
Seals: EPDM, Buna-N, Neoprene, FKM, or other
Body Material:
	¾" to 2":Brass (UNS C83600)
	3" to 8": Schedule 40, epoxy coated, carbon steel pipe

OUTPUT

Pulse Output: Can be factory set or field configured to report volume flow rate, mass flow rate or energy total. 
Output is an optically isolated NPN transistor with maximum sinking capability to 50 mA from a voltage source 
of no more than 48 VDC or a voltage output (power supply voltage). Pulse duration is 2 ms when reporting flow 
rate and 10 ms when reporting energy total (consult factory for different pulse duration).

Wiring Connection:

10 ft shielded 3-conductor plenum cable for RS-485
10 ft shielded 4-conductor plenum cable for power & pulse output
Liquidtight 1/2" non-metallic conduit connector supplied for RS-485 & Power & Pulse cable

Table 2

STANDARD MODELS- ¾" TO 2"
Model Pipe Size/Thread Size Full Scale Ranges (GPM) Full Scale Ranges (LPM)
Min. Max. Pulses/gallon Min. Max. Pulses/liter
CS-EMB34 3/4" NPT or BSP 0.38 25 1200 1.50 100 360
CS-EMB10 1.0" NPT or BSP 0.75 50 600 3.00 200 160
CS-EMB15 1.50" NPT or BSP 1.20 80 375 4.50 300 85
CS-EMB20 2.0" NPT or BSP 1.80 120 200 6.8 455 50

Table 3

STANDARD MODELS- 3" TO 10"
Model Pipe Size Full Scale Ranges (GPM) Full Scale Ranges (LPM)
Min. Max. Pulses/gallon Min. Max. Pulses/liter
CS-EMC3 3" 6 400 75 23 1500 20
CS-EMC4 4" 7.5 500 60 29 1900 16
CS-EMC6 6" 18 1200 25 68 4500 7
CS-EMC8 8" 30 2000 15 114 7600 4
CS-EMC10 10" 45 3000 10 165 11000 3

FIELD REPLACEABLE TRANSDUCER FOR 3" TO 10" SIZES

FIELD REPLACEABLE TRANSDUCER FOR 4” TO 10” SIZES
Transducer Components
1 Spring Retainer
2 Spring
3 Clamp
4 Bushing
5 Drywell
6 Ultrasonic Transducer

Two opposing CS-EMC ultrasonic transducers are inserted into fixed ULTEM® drywells and held in place with light spring force. A locating keyway in the drywell aids insertion and positioning of the transducers. In the event of field failure of a transducer, replacement is straightforward and can be accomplished without removing the pipe spool and shutting down the process.

The electrical PC board can also be field replaced. Calibration factor and other specific information are maintained at the factory for all transmitters shipped.

 

Energy Measurement:

T1 RTD is located in the flow sensor
T2 Remote RTD is installed in a return pipe.
Heating and cooling energy are both measured and totaled in separate registers in model CS-EM. The values can 
	be interrogated via the Modbus Master.
	1) Heating Mode: T1>T2
	2) Cooling Mode: T2>T1
The energy total pulse output functions in the absolute mode, indifferent as to whether in the heating or 
cooling mode.

Modbus Operability:

Baud Rate: 9600 (default) or 19.2 KB/S
Parity: Selectable, None (default), Even, Odd
Slave ID: 01-255 (default is 01)
Function Codes: 03, 05 & 06 are supported
Exception Codes: 01, 02 & 03 are supported
Data types: Word, Double
Data is sent "Big Endian", i.e. most significant byte first.
Flow and energy data updated every 2 seconds.
Turn around time is less than 2 seconds. Since the data is updated every 2 seconds, reading data at intervals 
	greater than the update time will ensure that current values will always be fresh.

Commissioning:

The CS-EM requires no special software to set the desired communication parameters. It can be done at the 
factory or from the user's Modbus Master over the RS-485 network. Standalone commissioning can be done 
via PC serial port (model 485SD9TB, RS-485 converter required). Download commissioning software HERE. 

Table 4

Read Data Registers
Variable Register Number # Registers Function Code Data Type Description
FLOW RATE 40001 2 03 Double RETURNS FLOW RATE IN SELECTED UNITS
ENERGY RATE 40003 2 03 Double RETURNS ENERGY RATE IN SELECTED UNITS
MASS RATE 40005 2 03 Double RETURNS MASS FLOW RATE IN SELECTED UNITS
FLOW TOTAL 40007 2 03 Double RETURNS TOTAL FLOW IN SELECTED UNITS SINCE LAST RESET
HEATING TOTAL 40009 2 03 Double RETURNS TOTAL HEAT ENERGY IN SELECTED UNITS SINCE LAST RESET
COOLING TOTAL 40011 2 03 Double RETURNS TOTAL COOLING ENERGY IN SELECTED UNITS SINCE LAST RESET
MASS TOTAL 40013 2 03 Double RETURNS TOTAL MASS IN SELECTED UNITS SINCE LAST RESET
LOCAL TEMP 40015 2 03 Double RETURNS LOCAL TEMPERATURE IN SELECTED UNITS
REMOTE TEMP 40017 2 03 Double RETURNS REMOTE TEMPERATURE IN SELECTED UNITS

Table 5

Setup Functions, Write Data Registers
Variable Register Number # Registers Function Code Data Type Description
SET FLOW RATE UNITS 40101 1 06 WORD UNITS OF FLOW RATE; 0 = G/M, 1 = L/M, 2 = L/SEC
SET ENERGY RATE UNITS 40102 1 06 WORD UNITS OF ENERGY RATE; 3 = BTU/M, 4 = KBTU/M, 5 = KBTU/HR, 6 = KW
SET MASS FLOW RATE UNITS 40103 1 06 WORD UNITS OF MASS RATE; 7 = LBS/MIN, 8 = KG/MIN
SET FLOW TOTAL UNITS 40104 1 06 WORD FLOW TOTAL UNITS; 9 = GALS, 10 = LITERS, 11 = CUBIC METERS
SET ENERGY TOTAL UNITS 40105 1 06 WORD ENERGY TOTAL UNITS; 12 = kBTU, 13 =W-HRS, 14 = KW-HRS
SET MASS TOTAL UNITS 40106 1 06 WORD MASS UNITS; 15 = LBS, 16 = KG
SELECT PULSE OUTPUT 40107 1 06 WORD SELECT ENERGY,FLOW,OR MASS AS PULSE OUTPUT; 0 = FLOW, 1 = ENERGY, 2 = MASS
SELECT TEMPERATURE UNITS 40108 1 06 WORD SELECT DEG F OR DEG C; 0 = DEG F, 1 = DEG C
SET % ETHYLENE GLYCOL 40109 1 06 WORD ENTER VALUE 0-30
SET % PROPYLENE GLYCOL 40110 1 06 WORD ENTER VALUE 0-30

Table 6

Commissioning & Other Functions, Write Data Registers
Function Register Number # Registers Function Code Data Type Description
*SET SLAVE ID 40201 1 06 WORD 01 IS FACTORY SET, 0 to 255
*BAUDRATE 40202 1 06 WORD 19.2 KB 0R 9600 (DEFAULT) 0 = 9600, 1 = 19.2kb
*SET PARITY 40203 1 06 WORD NONE, ODD, EVEN (DEFAULT) 0,1,2
RESET FLOW TOTAL 00001 1 05 WORD CLEARS TOTALIZED FLOW
RESET HEATING ENERGY TOTAL 00002 1 05 WORD CLEARS TOTALIZED HEATING ENERGY
RESET COOLING ENERGY TOTAL 00003 1 05 WORD CLEARS TOTALIZED COOLING ENERGY
RESET MASS TOTAL 00004 1 05 WORD CLEARS TOTALIZED MASS
SET DEFAULT UNITS 00005 1 05 WORD RESET ALL UNITS TO FACTORY DEFAULTS
*Can only be set when commissioning

Commissioning from a personal computer is straightforward with Clark commissioning software.
Download here.
Clark commissioning software. Pipe sizes 3/4" to 2"

Table 7

Dimensions - Pipe Sizes 3/4" to 2"
Size/ Connection A B C D E
Inches mm Inches mm Inches mm Inches mm Inches mm
3/4" & 1" 9.20 234 1.62 41.10 2.06 52.30 6.40 163 2.40 61.00
1-1/2" & 2" 9.88 251 2.75 69.90 2.51 63.80 6.40 163 2.40 61.00


4-10" Schedule 40 Carbon Steel Pipe, ASME 150 Flange

Table 8

Dimensions - Pipe Sizes 3" to 10"
Pipe Size Dimensions (Inches) Number of Holes
A B C D E F Bolt Circle Diameter
3" 11.00 7.50 3.50 6.54 2.62 0.75 6.00 4
4" 13.00 9.00 4.00 6.54 2.62 0.75 7.50 8
6" 16.00 11.00 5.09 6.54 2.62 0.88 9.50 8
8" 18.00 13.50 6.11 6.54 2.62 0.88 11.75 8
10" 22.00 16.00 7.18 6.54 2.62 1.00 14.25 12

ELECTRICAL

RS-485: 3-conductor cable
	Red: TXD1
	Black: TXDO
	Green or Clear: GND
Power & Pulse Out: 4-conductor cable
	 Red (+): Vin 12 to 30 VDC
	 Black (-): Vin Return
	 Green : OPTO NPN E
	 White: OPTO NPN C

Optional Model 43-119, RS-485 Converter for Commissioning 
from a PC
Optional Model 43-119, RS-485 Converter 
for Commissioning from a PC:
PC End: DB9 Female
RS-485 End: Terminal Block
Terminal Block Connections to DN-EM:
	Black: TD(A)-
	Red: TD(B)+
	Clear or Green: Gnd (Green)
 Pulse output wiring
Note:  NPN Opto-isolated switch output (order code I) 
and Vo Powered Pulse Output (order code V) are jumper 
selected at the factory.

ORDERING INFORMATION

Model CS-EM is supplied with a default setup configuration. The setup can be changed in 
the field (see CS-EM installation manual) or configured at the factory according to customer 
requirements. If you require the factory to provide a non-default configuration, please 
DOWNLOAD a Factory Configuration Sheet (PDF file)

To order a factory default configuration:

1) SELECT REMOTE TEMPERATURE SENSOR FROM TABLE 1
2) SELECT FLOW/ENERGY MONITOR FROM TABLES 2 OR 3

Table 9
3/4" TO 3" ENERGY METER ORDERING INFORMATION

ORDER NUMBER: ABCD
EXAMPLE: CS-EM10-19-027NE1

A=Flow Transmitter Model w/Remote Temp Probe B=Pipe Thread C=Transducer Seal D
1= Default Configuration #1 2= Default Configuration #2 3= Default Configuration #3
CS-EMB34-19-027 N= Female NPT E= EPDM Pulse Output: 1 pulse = 1000 Btu (1 KBtu) Pulse Output: 1 pulse = 1 KW-Hr User Specified:  User must download, fill out and submit the Factory Configuration Sheet.
CS-EMB10-19-027 B=Female British Standard Pipe (G) B= Buna-N Media: Water, no glycol Media: Water, no glycol
CS-EMB15-19-027 N= Neoprene® Volume Flow Rate Units: Gallons/Min Volume Flow Rate Units: Liters/Min
CS-EMB20-19-027 V= FKM Mass Flow Rate Units: Lbs/Min Mass Flow Rate Units: KG/Min
Volume Total Units: Gallons Volume Total Units: Liters
Mass Total Units: Lbs Mass Total Units: KG
Energy Rate Units: kBtu/Min Energy Rate Units: KW
Energy Total Units: kBtu Energy Total Units: KW-Hrs
Temperature Units: oF Temperature Units: oC
Baud Rate: 9600 Baud Rate: 9600
Parity: None Parity: None
Slave ID: 01 Slave ID: 01
See Table 1 for Temperature Probe detail.
See Table 2 for Flow Transmitter Model detail.

Table 10
3" TO 10" ENERGY METER ORDERING INFORMATION

ORDER NUMBER: ACD
EXAMPLE: CS-EMC4-19-028E2

A= Flow Transmitter Model w/Remote Temp Probe C= Transducer Seal D
1= Default Configuration #1 2= Default Configuration #2 3= Default Configuration #3
CS-EMC3-19-028 E= EPDM Pulse Output: 1 pulse = 1000 Btu (1 KBtu) Pulse Output: 1 pulse = 1 KW-Hr User Specified:  User must download, fill out and submit the Factory Configuration Sheet.
CS-EMC4-19-028 B= Buna-N Media: Water, no glycol Media: Water, no glycol
CS-EMC6-19-029 N= Neoprene® Volume Flow Rate Units: Gallons/Min Volume Flow Rate Units: Liters/Min
CS-EMC8-19-029 V= FKM Mass Flow Rate Units: Lbs/Min Mass Flow Rate Units: KG/Min
CS-EMC10-19-030 Volume Total Units: Gallons Volume Total Units: Liters
Mass Total Units: Lbs Mass Total Units: KG
Energy Rate Units: kBtu/Min Energy Rate Units: KW
Energy Total Units: kBtu Energy Total Units: KW-Hrs
Temperature Units: °F Temperature Units: °C
Baud Rate: 9600 Baud Rate: 9600
Parity: None Parity: None
Slave ID: 01 Slave ID: 01
See Table 1 for Temperature Probe Detail.
See Table 3 for Flow Transmitter Model detail.

ULTEM® is a registered trademark of The General Electric Company.
Neoprene® is a registered trademark of DuPont Dow.

Table 11
ACCESSORIES ORDERING INFORMATION

Accessory Description
RT-3-502 RTD cable, 1 ft, three conductor , 22 gauge stranded tinned, PVC insulation, red, red, white; outer insulation color white, temp rating 221°F
43-119 RS-485 Converter for Commissioning from a PC
CS-EM BTU/Energy Monitor


Download
Commissioning Software