CSLFB Liquid Ultrasonic Flow Transmitters
Loop Powered 4-20 mA Output, Flows to 400 GPM, 3/4" to 3" Pipe, Brass
DESCRIPTION
Clark Sonic® ultrasonic flow transmitters are ideal for measurement of flow rates of acoustically conductive liquids, including most clean liquids and many liquids with entrained solids.
Main advantages include excellent long term stability, no pressure drop,
broad fluid compatibility, high accuracy and low cost. Also, there are no moving parts.
At the heart of the transmitter is a proprietary mixed signal ASIC which
allows sophisticated timing, control and transducer drive circuitry to be combined
on a single integrated circuit. The ASIC uses a special algorithm that is an
improvement upon the standard single-path measurement technique. Using the
"sing around" method, the ultrasonic transducer alternates between transmitting
and receiving to measure differences in flight time between upstream and downstream
transmissions. A sound pulse is transmitted from an upstream transducer towards a
downstream transducer like a traditional time-of-flight measurement. However, the
received sound pulse then triggers a second downstream transmission that then
triggers a third and so on for a specific number of cycles. This process is
repeated in the upstream direction.
Because it takes an average flight time over multiple cycles to compute the
difference in flight times, the approach yields a significant improvement in timing
accuracy when compared with the time-of-flight difference of a single sound pulse in
each direction. This algorithm, combined with the pico-second timing resolution of the
ASIC, provides the precise time measurement capability necessary for compact, small
diameter ultrasonic meters.
The output of the transmitter is unaffected by changes in fluid temperature, density
and viscosity as the flow calculation is independent of the speed of sound.
Wetted materials include ULTEM® encapsulated ultrasonic transducers with a choice
of elastomer seals and Brass body material.
SPECIFICATIONS
GENERAL
Flow Range: Bi-directional, field selectable per "Standard Models" table
Accuracy: ±.75% of full scale
Operating Temperature: -40 to 190°F (-40 to 87.8°C)
Response Time: User Selectable, 2 or 10 seconds
Viscosity Range: 0.2 to 150 cSt (0.2 to 150 mPas)
Liquid Density: 30.6 to 74.9 lb/cu.ft. (490 to 1200 kg/m3)
Max. Working Pressure: 250 PSI (17.2 bars)
Pipe Sizes: 3/4", 1", 1 1/2", 2", 3"
Pipe Connections:
Sizes 3/4" to 2"- Female NPT, BSP
Size 3": ASME 150 or DIN 16 Flange
Electrical Enclosure: Integral to Body casting with gasketed cover; One 1/2"
NPT conduit connection (plugged when model ordered with metric threads)
and one M16 x 1.5 connection (plugged when model ordered with NPT threads)
Electrical Connections: Screw terminal connections on PC board
Enclosure Rating: NEMA 4 (IP 65)
Power: 18 to 36 VDC
WETTED MATERIALS
Ultrasonic Transducers: ULTEM® Encapsulated
Seals: EPDM, Buna-N, Neoprene™, FKM, or other
Body Material: Brass (UNS C83600)
OUTPUT
Analog: 2-wire, 4-20 mA output; Output is 4 mA from zero to min. flow
(see Standard Model table)
Error Detection: An optically isolated sink output is activated under
certain detectable fault conditions, such as transducer failure or
overly noisy output due to flow stream anomalies, as might be seen
due to excessive bubble entrainment. The optional Fault output is
an optically isolated NPN transistor capable of sinking up to 10 mA
from a voltage source of no more than 48 VDC.
Direction of Flow: Optional output to indicate direction of flow is
available. Activation or deactivation of an optically isolated 10 mA
sink output indicates flow direction. Error detection is not available
when this option is ordered.
Optional Temperature Sensor: 3 wire RTD, 100 Ohm, Platinum, 0.06% accuracy.
Built in to transducer shell for monitoring process temperature.
Optional 8 pin electrical connector standardly recommended with this option.

|
Optional NEMA 4 four or
eight-pin receptacles installed in
transmitter conduit connection and
factory wired along with mating circular
connectors simplify field installation. |
| Size/Connection |
A |
B |
C |
D |
E |
| Inches |
mm |
Inches |
mm |
Inches |
mm |
Inches |
mm |
Inches |
mm |
| 3/4" & 1" |
9.20 |
234 |
1.62 |
41.10 |
2.06 |
52.30 |
6.40 |
163 |
2.40 |
61.00 |
| 1-1/2" &
2" |
9.88 |
251 |
2.75 |
69.90 |
2.51 |
63.80 |
6.40 |
163 |
2.40 |
61.00 |
| Size/Connection |
A |
B |
C |
D |
E |
| Inches |
mm |
Inches |
mm |
Inches |
mm |
Inches |
mm |
Inches |
mm |
| 3" ASME
150 |
11.00 |
- |
Ø 7.50 |
- |
3.16 |
- |
6.50 |
- |
2.50 |
- |
|
80 mm DIN 16 |
- |
280 |
- |
190 |
- |
84.00 |
- |
165 |
- |
63.50 |
STANDARD MODELS
|
Model |
Pipe Size/Thread Size |
*Field Selectable Full Scale Ranges (GPM) |
*Field Selectable Full Scale Ranges (LPM) |
| |
Min. |
Max. |
Min. |
Max. |
|
CSLFB34 |
3/4" NPT or BSP |
L |
0.23 |
15 |
0.90 |
60 |
| H |
0.38 |
25 |
1.50 |
100 |
|
CSLFB10 |
1.0" NPT or BSP |
L |
0.45 |
30 |
1.70 |
115 |
| H |
0.75 |
50 |
3.00 |
200 |
|
CSLFB15 |
1.50" NPT or BSP |
L |
0.60 |
40 |
2.30 |
150 |
| H |
1.20 |
80 |
4.50 |
300 |
|
CSLFB20 |
2.0" NPT or BSP |
L |
0.90 |
60 |
3.40 |
225 |
| H |
1.80 |
120 |
6.80 |
455 |
|
CSLFB30 |
3" ASME Class 150 Flange 80 mm DIN
Class 150 Flange |
L |
3.00 |
200 |
11.00 |
750 |
| H |
6.00 |
400 |
23.00 |
1500 |
|
*Other F.S. ranges can
be specified |
DP/DS PANEL METER/DISPLAY OPTION
Digital panel meter installed on transmitter
Power Supply: Loop Powered
Display: 4-1/2 Digit LED, 0.6"
Case: NEMA 4X
Versions: DP Option: Displays 0-100% F.S
DS Option: Scaled to customer requirement

|
|
|
Panel Meter/Display option
Four or eight pin receptacle connector recommended.
|
| |
ORDERING INFORMATION
ORDER NUMBER (ABCD)
Example: CSLFB10NPTGB
| FOR YOUR CONVENIENCE, THESE ITEMS ARE AVAILABLE ONLINE OR PLEASE CALL 1-800-253-2497 TO ORDER |
| A |
B |
C |
D |
| Model |
Pipe Thread |
Units of Measure |
Transducer Seal |
| 3/4" to 2" |
3" |
| CSLFB34 |
NPT= Female NPT |
ASME= ASME Class 150 Flange |
G= Gallons Per Minute (U.S.) |
E= EPDM |
| CSLFB10 |
B = Buna-N |
| CSLFB15 |
BSP=Female British Standard Pipe (G) |
DIN = DIN Class 16 Flange |
L = Liters Per Minute |
N= Neoprene® |
|
CSLFB20 |
V= FKM |
| CSLFB30 |
| |
| Options |
| -= None |
| DF= Direction of flow output option, call factory at 1-800-253-2497 to order. |
| R=100 OhmPlatinum RTD |
| DP=Display % F.S |
| DS=Display in Engineering Units- specify |
| |
| Transmitter Connector Option |
| -= 1/2" NPT |
| 4R= 4-Pin Male Circular Receptacle |
| 8R= 8-Pin Male Circular Receptacle |
| 4C= 4-Pin Female Circular Connector |
| 8C= 8-Pin Female Circular Connector |
| |
| *For non-listed ranges specify model followed by full span value |
| Example: CSLFB15-50G = 50 GPM at 20 mA or CSLFB15-200L=200LPM @ 20 mA |
ULTEM
® is a registered trademark of The General Electric Company
Neoprene
® is a registered trademark of DuPont Dow
Clark reserves the right to make design changes without prior notice.