Valves >> General Purpose Solenoid Valve >> Model 1323, 3-Way Solenoid Valve
Model1323_3-Way Valve

CLARK SOLUTIONS

Model 1323, 3-Way Solenoid Valve


1/4” Pipe Size, Direct Acting Solenoid

DESCRIPTION
Model 1323 three-way solenoid valves are available in brass, 304 or 316 stainless steel bodies. A variety of seal and seat materials including Acrylo-Nitrile, Neoprene®, Ethylpropylene and Viton® satisfy many general industry applications.

The valves employ a direct acting solenoid. A choice of solenoids cover a range of ambient temperatures and operating voltages.

Options include weather proof housing, energized coil indicator light and manual override


SPECIFICATIONS
GENERAL
Operation: 3-way, two positions (N.C., N.O.,
      divergent, convergent, universal)
Valve Body: Brass, AISI304 stainless steel,
      AISI316 stainless steel
Valve Life: > 1,000,000 cycles, field rebuild kits
      available
Valve Seals & Seats: See Table 2
Connections: 1/4” BSP or NPT
Operating Voltage - 12 VDC, 24 VDC/VAC,
      120 VAC, 60Hz
Standard Solenoid Housing: Encapsulated,
      includes DIN 43650 connector (PG-9)
Connector Wire Connection: Screw terminal
Optional IP65/NEMA4 Weather Proof:
      Encapsulated coil, 1/2” NPT potted conduit
      connection with flying leads
Coil Rating:
      Class F coil to 80ºC: AC 60 Hz,
      13 W; DC, 19 W
      Class H Coil to 180ºC: AC 60 Hz,
      13 W;DC,19 W
Options: Manual operation, weatherproof
      housing, energized coil indicator light
Weight: 0.5 kg

Table 1
Wetted Materials
Body Plunger Plunger Tower Springs
Brass AISI 430F 304L or 305 SS Copper
AISI 304 AISI 430F 304L or 305 SS Silver & 302 SS
AISI 316 AISI 430F 304L or 305 SS Silver & 302 SS
Table 2
Seat Material Acrylo Nitrile Neoprene® Ethyl-propylene Viton®
Maximum Temperature +80ºC +80ºC +150ºC +150ºC
Uses Water, air, light oils, kerosene. Low and medium vacuum. Oxygen, alcohol, argon, other non-corrosive light gases and liquids. Freon 12. Water steam, hot water, acetone. Benzene, naphtha, aromatics, etc.. Hot gases. High vacuum.
Orifice Diameter Cv (GPM) Kv (m3/h Max. Differential Pressure (bar) by Configuration
N.C. N.O. DIV CONV.
Three-Way, Two Position, "C" Construction (See Model Number Table), N.C., No Connector at "C" Outlet
1.75

 

0.09 10 - - -
2.00

 

0.10 7 - - -
2.50

 

0.14 3 - - -
Three-Way, Two Position,"D" Construction (See Model Number Table), Divergent
1.75

 

0.09 10 - 20 -
2.00

 

0.10 7 - 15 -
2.50

 

0.14 3 - 10 -
Three-Way, Two Position, "A" Construction (See Model Number Table), N.O.
1.75

 

0.09 5 12 5 5
2.00   0.10 3 10 3 3
2.50   0.14 - 3 - -
Three-Way, Two Position, "U" Construction (See Model Number Table), Universal
1.75   0.09 8 12 20 8
2.00   0.10 6 10 15 6
2.50   0.14 3 3 10 3
Install in any position, preferably on a horizontal run of pipe with coil upright. Except “C”, all constructions may be used for any configurations but it is desirable to select the valve according to its use to obtain the best performance.
Flow Calculation, Liquids:

Q= Flow Rate, GPM (U.S.A.)
Cv= Valve Flow Coefficient
DP= Valve Pressure Drop, PSID
G= Specific Gravity of Liquid (= 1.0 for Water)

Option YC Weather Proof Housing with 1/2” NPT Threaded Conduit Connector
Standard Coil and DIN43650 Connector
ORDERING INFORMATION
SELECT ITEM FROM EACH COLUMN IN CHART BELOW
EXAMPLE: 1323SV17ATF24DC
FOR YOUR CONVENIENCE, THESE ITEMS ARE AVAILABLE ONLINE
Model Body Material Seat & Seal Material Orifice Size (mm) Construction (See Above Table) Connection Threads Coil Type Voltage
1323 B= Brass A= Acrylo-Nitrile 17= 1.75 U= U Construction T= NPT F= Class F 12DC= 12 VDC
S= 304 SS V= Viton 120AC= 120 VAC, 60 HZ
24DC= 24 VDC
 
Options
Prefix YC= Weather Proof Housing (1/2” NPT Thread)
Bold Order Combinations Typically Ship From Stock

Qty:

Show Discount Schedule


OR PLEASE CALL 1-800-253-2497 TO ORDER THESE ITEMS
Model Body Material Seat & Seal Material Orifice Size (mm) Construction (See Above Table) Connection Threads Coil Type Voltage
1323 B= Brass A= Acrylo-Nitrile 17= 1.75 U= U Construction T= NPT F= Class F 12DC= 12 VDC
S= 304 SS V= Viton 20=2.00 C= C Construction - = BSP  H= Class H 120AC= 120 VAC, 60 HZ
I= 316 SS N= Neoprene 25= 2.50 D= D Construction     24DC= 24 VDC
  E= Ethylpropylene   A= A Construction 24AC= 24 VAC, 60 HZ
 
Options
Prefix YC= Weather Proof Housing (1/2” NPT Thread)
Suffix M= Manual Operation
Coil Indicator Light= Consult Factory
Bold Order Combinations Typically Ship From Stock
INSTALLATION RECOMMENDATIONS
Place a strainer with a porosity < 100µ upstream of valve (see Clark Solutions Model 1359 Y Strainer).