DESCRIPTION
Model 1335 two-way normally closed and normally open solenoid valves are available in forged brass or 316 stainless steel bodies. A variety of seal and seat materials including Acrylo-Nitrile, Neoprene®, Ethylpropylene, and Viton® satisfy many general industry applications.

Options include weather proof coils & housing, manual override and energized coil indicator light.

SPECIFICATIONS
GENERAL
Operation: Normally closed or normally open
Valve Body Materials: Forged brass, investment
       cast AISI316 stainless steel
Diaphragm: Metal core with choice of seat
       material
Valve Seats: Acrylo-Nitrile, Neoprene®,
       Ethylpropylene, Viton®
Valve Life: > 1,000,000 cycles, field rebuild kits
       available
Connections: BSP or NPT
Operating Voltage - 12VDC, 24VDC/VAC,
       120VAC, 60Hz
Standard Solenoid Housing: Encapsulated coil,
       DIN 43650 connection (PG-9)
Optional Weather Proof Solenoid Housing: NEMA
       4, IP65
Power Consumption:
    Class F coil to 80ºC: 60 Hz, 13 W; DC,19 W
Options: Manual operation, energized coil
       indicator light

Table 1
Wetted Materials
Body Plunger Plunger Tower Springs Diaphragm Inner-Diaph. Material Piston
Brass AISI 430F 304L or 305 SS Copper See Table 2 - AISI 304
AISI 316 AISI 430F 304L or 305 SS Silver & 302 SS See Table 2 AISI 316 AISI 316
Table 2
Seat Material Acrylo Nitrile Neoprene® Ethyl-propylene Viton®
Maximum Temperature +80ºC +80ºC +150ºC +150ºC
Uses Water, air, light oils, kerosene. Low and medium vacuum. Oxygen, alcohol, argon, other non-corrosive light gases and liquids. Freon 12. Water steam, hot water, acetone. Benzene, naphtha, aromatics, etc.. Hot gases. High vacuum.
File LR87427 2M - LR108921-1
File MH16855 Vol. 2 Sec. 2
Connection (NPT or BSP) Orifice Dia. (mm) Cv Coef. (GPM) Kv Coef. (m3/h) Weight (kg)
Brass Body, Pilot Operated, Normally Closed: Minimum Differential, 0.1 Bar; Maximum Differential Pressure, 10.0 Bar
3/8" 14 2.75 2.35 0.76
1/2" 14 3.10 2.65 0.76
3/4" 18 5.03 4.30 0.98
Brass Body, Combined Acting, Normally Closed: Minimum Differential, 0 Bar; Maximum Differential Pressure, 7.0 Bar
3/8" 14 2.75 2.35 0.76
1/2" 14 3.10 2.65 0.76
3/4" 18 5.03 4.30 0.98
Brass Body, Pilot Operated, Normally Open: Minimum Differential, 0.1 Bar; Maximum Differential Pressure, 10.0 Bar
3/8" 14 2.75 2.35 0.76
1/2" 14 3.10 2.65 0.76
3/4" 18 5.03 4.30 0.98
DIMENSIONS MM
A
NPT or BSP
B
N.C.
B
N.O.
C D E F
3/4” 80 88 15 51 60 53
1”
1, 1/2” 82 90 17 58 72 55
FUNCTION
Piloted valves use the fluid pressure to assist in opening and closing the valve, allowing the valve to operate against higher pressures than a direct acting valve.

When the pilot valve is closed, the pressure builds up via a small passage from the upstream side of the valve piston/seat. The valve seat is also acted on by a spring.

When the pilot valve opens, a passage that bypasses the valve piston/seat and connects downstream of the piston/seat is opened, relieving pressure from the top of the valve piston/seat. The inlet fluid pressure lifts up the piston to open the valve.

Flow Calculation, Liquids:

Q= Flow Rate, GPM (U.S.A.)
Cv= Valve Flow Coefficient
DP= Valve Pressure Drop, PSID
G= Specific Gravity of Liquid (= 1.0 for Water)

Standard Coil and DIN43650 Connector Option YC Weather Proof Housing with 1/2” NPT Threaded Conduit Connector
ORDERING INFORMATION
SELECT ITEM FROM EACH COLUMN IN CHART BELOW
EXAMPLE:1335BN3AT12DC
FOR YOUR CONVENIENCE, THESE ITEMS ARE AVAILABLE ONLINE
Model Body Material Seat & Seal Material Pipe Connection Configuration Connection Threads Voltage
1335   B= Brass A= Acrylo-Nitrile 3= 3/8” - = Pilot operated, Normally Closed T= NPT 12DC= 12 VDC
V= Viton 4= 1/2” 120AC= 120 VAC, 60 Hz
  6= 3/4” 24DC= 24VDC
 
Options
Prefix YC= Weather Proof Housing (1/2" NPT Thread)
Bold Order Combinations Typically Ship From Stock

Qty:

Show Discount Schedule


OR PLEASE CALL 1-800-253-2497 TO ORDER THESE ITEMS
Model Body Material Seat & Seal Material Pipe Connection Configuration Connection Threads Voltage
1335   B= Brass A= Acrylo-Nitrile 3= 3/8” - = Pilot operated, Normally Closed T= NPT 12DC= 12 VDC
I= 316 SS V= Viton 4= 1/2” A = Combined Acting, Normally Closed  - = BSP 120AC= 120 VAC, 60 Hz
  N= Neoprene 6= 3/4” INA = Pilot operated, Normally Open   24DC= 24VDC
E= Ethylpropylene     24AC= 24 VAC, 60 Hz
 
Options
Prefix YC= Weather Proof Housing (1/2" NPT Thread)
Suffix M= Manual Operation
Coil Indicator Light= Consult Factory
Bold Order Combinations Typically Ship From Stock

INSTALLATION RECOMMENDATIONS
Place a strainer with a porosity < 100µ upstream of valve (see Clark Solutions Model 1359 Y Strainer).
Install valve in any position, preferably on a horizontal pipeline with coil up.