EN132-177-310Actuator CLARK SOLUTIONS
EN132, EN177 & EN310 Non-Spring Return Electric Actuators
On/Off, Tri-State, & Modulating, 132, 177 & 310 in-lb

The EN132C2(-S), EN177C2(-S) and EN310C2(-S) direct coupled 24 VAC non-spring return (NSR) rotary electronic actuators are designed for tri-state (floating) or two-position control of building HVAC dampers and valves.

The EN132B2, EN132B2-ZS-S, EN177B2(-S), EN177B2-ZS(-S), EN177D2(S), EN310B2(-S), EN310B2-ZS(-S) and EN310D2(-S) direct coupled 24 VAC non-spring return (NSR) rotary electronic actuators are designed for modulating control of building HVAC dampers or valves.

These actuators are used in constant or variable air volume installations for the control of return air, mixed air, exhaust, and face and bypass dampers and valves requiring up to 132 in-lb (15 N-m), 177 in-lb (20 N-m), or 310 in-lb (35 N-m) torque.

WIRING & COMPONENTS
1. Positioning scale for angle of rotation
2. Manual override (push)
3. Span adjustment (-ZS version)
4. Offset (start point) adjustment(-ZS version)
5. Connection cables
6. Mounting bracket
7. Auxiliary switch B (-S option)
8. Auxiliary switch A (-S option)
9. Position indicator
10. Standard or self-centering shaft adapter*
11. Shaft adapter locking clip
12. Position indicator adapter

* Self-centering shaft adaptor shown

OPERATION
Two Position or Tri-state: A floating control signal controls the actuator. The actuator’s angle of rotation is proportional to the length of time the signal is applied. A 24 VAC control signal to wire 6 causes the actuator coupling to rotate clockwise.  A 24 VAC control signal to wire 7 causes the actuator coupling to rotate counterclockwise. Reverse the position indicator so that the counterclockwise 0 to 90 scale is visible, if needed.

In the event of a power failure, or with no control voltage, the actuator holds its current position.

An improperly-tuned control loop will cause excessive repositioning that will shorten the life of the actuator.

Modulating Type: A continuous 0 to 10 VDC signal from a controller to wire 8 operates the actuator. The angle of rotation is proportional to the control signal. A 0 to 10 VDC position feedback output signal is available between wires 9 and wire 2(com) to monitor the position of the motor.

In the event of a power failure the actuator holds its position.

In the event only the control signal is lost, the actuator returns to the “0 ” position.

PLEASE CALL 1-800-253-2497 TO ORDER THESE ITEMS
24 VAC Operating Voltage Torque Input Signal Cabling
Standard With Dual Auxiliary Switches & Potentiometer Dual Auxiliary Switches only Span/Offset Adjustable Dual Aux. Switches and Span/Offset Adjustable
EN132C2 EN132C2-S - - - 132 in-lb min. (15 N-m) Tri-state or two-position Std. or Plenum
EN177C2 EN177C2-S - - - 177 in-lb min. (20 N-m) Tri-state or two-position Plenum Cabling
EN310C2 EN310C2-S - - - 310 in-lb min. (35 N-m) Tri-state or two-position Plenum Cabling
EN132B2 - - - EN132B2-ZS-S 132 in-lb min. (15 N-m) 0-10 VDC 0-20 mA Std. or Plenum
EN177B2 - EN-177B2-S EN177B2-ZS EN177B2-ZS-S 177 in-lb min. (20 N-m) 0-10 VDC 0-20 mA Plenum Cabling
EN177D2 - EN177D2-S - - 4-20 mA Plenum Cabling
EN310B2 - EN310B2-S EN310B2-ZS EN310B2-ZS-S 310 in-lb min. (35 N-m) 0-10 VDC Plenum Cabling
EN310D2 - EN310D2-S - - 4-20 mA Plenum Cabling

Specifications EN132C2(S) EN177C2(S) EN310C2(S) EN132B2(ZS)(S) EN177B2(ZS) EN310B2(ZS)(S) EN177D2(S) EN310D2(S)
Power supply 24 VAC ±20% 24 VAC ±15%, 50/60 Hz 24 VAC ±20% 24 VAC ±15%, 50/60 Hz
Transformer sizing  (class 2 power source required for UL)
Power consumption 3 VA running 4 VA running 6 VA running 5 VA running 4 VA running 6 VA running 4 VA running 6 VA running
Electrical connection 3 ft 18 AWG plenum cable
 Control signal "Y" - - - 0-10 VDC, 0-20 mA(add 500 ohm, 1/4 w resistor across pins 2 & 8) 4-20 mA
Input resistance - - - >100 Kohm 100 Kohm 500 ohms
Operating range - - - 0-10 VDC, 0-20 mA 4-20 mA
Feedback signal - - - 0-10 VDC, 1 mA max.
Overload protection electronic throughout 0° to 95° rotation
Potentiometer 0-1000 Ohms<10mA 0-1000 Ohms, max. 1 mA - - - - -
Manual override push down button
Angle of rotation mechanically limited to 95º 90 to 95º max.
Minimum torque 132 in-lb min. 177 in-lb 310 in-lb min. 132 in-lb min. 177 in-lb 310 in-lb min. 177 in-lb 310 in-lb min.
Direction of rotation selectable by dip switch
Position indication Visual Indicator, -5º to 90º (-5o is spring return position) visual indicator, 0 to 90º
Shaft size 1/4" to 3/4" dia.
1/ 4" to 1/2"sq
3/8" to 1" dia.
1/4" to 3/4"sq
1/4" to 3/4" dia.
1/ 4" to 1/2"sq
3/8" to 1" dia. 1/4" to 3/4"sq
Minimum shaft length 3/4" (20 mm)
– Auxiliary switches (-S option) 24 to 250 VAC, 6 A res 12 to 30 VDC, 2A Plenum 4A resistive, 24 VAC
Plenum 2A inductive, 24 VAC
24 to 250 VAC, 6 A resistive Plenum 4A resistive, 24 VAC
Plenum 2A inductive, 24 VAC
Switch range (-S option)
  – Switch A 0° to 90° with 5° intervals
  – Rec. range usage 0° to 45°
  – Factory setting
  – Switching hysteresis
Switch range (-S option)
  – Switch B 0° to 90° with 5° intervals
  – Rec. range usage 45° to 90°
  – Factory setting 85°
  – Switching hysteresis
Running time for 90º 125 secs at 60 Hz
150 secs at 50 Hz
120 secs 125 secs at 60 Hz
150 secs at 50 Hz
150 secs
Humidity  95% RH noncondensing
Housing type NEMA type 1/IP40 according to EN60529; NEMA 4/4xhousings available on request
Housing material Diecast aluminum
Ambient temperature  -25°F to 130°F (-32°C to 55°C)
Storage temperature -25°F to 158°F (-32°C to 70°C) -40°F to 158°F (-40°C to 70°C)
Noise level max. 40 dBA max. 45 dBA
Servicing maintenance free
Agency ratings UL 873 or UL60730 listed, CE-UL certified to CSA C22.2 No. 24-93
CE conformity
Immunity
EMC: 89/336/EEC, Emissions: EN5081-1
EN61000-6-2 except EN50082-1 IEN50082-2
Quality standard ISO 9002
Weight 2.2 lbs (1.0 kg) 4.4 lbs (2.0 kg)  2.2 lbs (1.0 kg)  4.4 lbs (2.0 kg)