EN44-88Actuator CLARK SOLUTIONS
EN44 & EN88 Non-Spring Return Electric Actuators

On/Off, Tri-State, & Modulating, 44 & 88 in-lb

The EN44C2 and EN88C2 direct coupled 24 VAC non-spring return rotary electronic actuators are designed for tri-state (floating) control or two position control (with external relay) of valves and dampers. They may be used in applications requiring up to 44 in-lb (5 N-m) of torque or 88 in-lb (10 N-m) of torque.

Models EN44B2 and EN88B2 direct coupled 24 VAC non-spring return rotary electronic actuators are designed for modulating control of dampers or valves. They may be used in applications requiring up to 44 in-lb (5 N-m) of torque or 88 in-lb (10 N-m) of torque.

WIRING & COMPONENTS
1.Base plate
2.Positioning scale for angle of rotation
3.Slope adjustment ("-ZS" version)
4.Offset (start point) adjustment ("-ZS" version)
5.DIP switches
6.Cover for DIP switches
7.Connection cables
8.Connection cables ("-S"option)
9.Manual override
10.Coupling bushing
11.Centering element for EN44 and(EN88 shaft diam 0.8 mm to 10 mm)
12.Auxiliary switch A ("-S" option)
13.Auxiliary switch B ("-S" option)
14.Position indicator
15.Adjustment lever with locking screw
16.Adjusting screw for mechanical range stop
17.Mounting bracket

OPERATION
Two Position or Tri-state: A floating control signal controls the actuator. The actuator’s angle of rotation is proportional to the length of time the signal is applied. A 24 VAC control signal to wire 6 causes the actuator coupling to rotate clockwise.  A 24 VAC control signal to wire 7 causes the actuator coupling to rotate counterclockwise. In the event of a power failure, or with no control voltage, the actuator holds its current position.

An improperly-tuned control loop will cause excessive repositioning that will shorten the life of the actuator.

Modulating Type: A continuous 0 to 10 VDC signal from a controller to wire 8 operates the actuator. The angle of rotation is proportional to the control signal. A 0 to 10 VDC position feedback output signal is available between wires 9 and wire 2 (com) to monitor the position of the motor.

In the event of a power failure the actuator holds its position.  In the event only the control signal is lost, the actuator returns to the “0” position.

PLEASE CALL 1-800-253-2497 TO ORDER THESE ITEMS
Actuator Model Number Table
24 VAC Operating Voltage Torque Input Signal Cabling
Standard With Potentiometer Dual Auxiliary Switches Only Span/Offset Adjustable Dual Aux. Switches and Span/Offset Adjustable
EN44C2 EN44C2-P EN44C2-S - - 44 in-lb min. (5 N-m) Tri-state or two-position Plenum Cabling
EN44C2-NP - - - - 44 in-lb min. (5 N-m) Tri-state or two-position Non-plenum Cabling
EN88C2 EN88C2-P EN88C2-S - - 88 in-lb min. (10 N-m) Tri-state or two-position Plenum Cabling
EN44B2 - EN44B2-S EN44B2-ZS EN44B2-ZS-S 44 in-lb min. (5 N-m) 0-10 VDC 0-20 mA Plenum Cabling
EN88B2 - EN-88B2-S EN88B2-ZS EN88B2-ZS-S 88 in-lb min. (10 N-m) 0-10 VDC 0-20 mA Plenum Cabling
Specifications EN44C2-NP, EN44C(S,P) EN88C2(S,P) EN44B2(S), EN44B2-ZS(S) EN88B2(S), EN88B2-ZS(S)
Power supply 24 VAC +20%, -15% 50/60 Hz
Transformer sizing  2.3 VA (class 2 power source req. for UL) 3.3 VA (class 2 power source req. for UL, class III per EN60730)
Electrical connection (-NP) Non-Plenum cable Standard: 3 ft plenum rated cable; conduit connector optional 3 ft 18 AWG plenum cable
Control signal "Y" - - 0-10 VDC, 0-20 mA†
Input resistance - - 100 Kohm VDC
Operating range - - 0-10 VDC, 0-20 mA†
Feedback signal - - 0-10 VDC, 1 mA Max
Angle of rotation 0° to 95°, adj. stops
Torque at rated voltage 44 in-lb min. (5 N-m) 88 in-lb min. (10 N-m) 44 in-lb min. (5 N-m) 88 in-lb min. (10 N-m)
Direction of rotation reversible with wiring reversible w/dip switch, factory setting is clockwise, with position feedback signal
Position indication clip on indicator

Shaft size

3/8" to 5/8" (8 mm to 16 mm) round
1/ 4" to 1/2" (6 mm to 12.7 mm) square
9/16" (15 mm) hex
Minimum shaft length 3/4" (20 mm)
Auxiliary features

–Feedback potentiometer
(-P option)

0 to 1000 Ohms, <10 mA    

– Auxiliary switches (-S option)

plenum: 4 A resistive, 24 VAC
plenum: 2 A inductive, 24 VAC

–Control Signal Adjustment (ZS option)

- 0-5 VDC

-Offset (start point)

-Slope

- 2-30VDC

Switch range (-S option)

– Switch A

0° to 90° with 5° intervals

– Recommended range usage

0° to 45°

– Factory setting

– Switching hysteresis

Switch range (-S option)

– Switch B

0° to 90° with 5° intervals

– Recommended range usage

45° to 90°

– Factory setting

85°
– Switching hysteresis
Running time 90 secs at 60 Hz
(108 secs at 50 Hz)
125 secs at 60 Hz (155 secs at 50 Hz) 90 secs at 60 Hz
(108 secs at 50 Hz)
125 secs at 60 Hz (155 secs at 50 Hz)
Humidity 95% RH noncondensing
Housing type NEMA type 2/IP54 according to EN60529; NEMA 4/4X housings available on request
Housing material Durable plastic
Ambient temperature -22°F to 130°F (-30°C to 55°C)
Storage temperature -22°F to 140°F (-30°C to 60°C)
Noise level <35 dBA
Servicing maintenance free
Agency ratings UL 873 listed, CE-UL certified to CSA C22.2 No. 24-93
CE conformity Electromagnetic Compatibility (EMC): 89/336/EEC
Emissions standards: EN50081-1
Immunity standards: EN50082-2
Quality standard ISO 9002
Weight 1.06 lbs (0.48 kg)

For assistance call 978-568-3400