EN132-177-310Actuator CLARK SOLUTIONS
ES62, ES75 & ES142 Spring Return Electric Actuators
Tri-State, & Modulating, 132, 177 & 310 in-lb

The ES62C2(-S)(24 VAC/VDC), ES75C2(-S) and ES142C2(-S) direct coupled 24 VAC spring return electronic actuators are designed for tri-state (floating) control of building HVAC dampers and valves.

The ES62B2(-S), ES62B2-ZS(-S), ES75B2(-S), ES75B2-ZS(-S), ES142B2(-S), ES142B2-ZS(-S) & ES142D2(-S) direct coupled 24 VAC spring return electronic actuators are designed for modulating control of building HVAC dampers and valves.

These actuators are used in constant or variable air volume installations for the control of return air, mixed air, exhaust, and face and bypass valves or dampers requiring up to 62 in-lb (7 N-m), 75 in-lb (8.5 Nm) or 142 in-lb (16 Nm) torque.  They are designed for applications that require the valve or damper to return to a fail-safe position when there is a power failure.

WIRING & COMPONENTS
1. Positioning scale for angle of rotation
2. Manual override wrench opening and direction of
        rotation arrow
3. Span adjustment (-ZS version)
4. Offset (start point) adjustment (-ZS version)
5. Connection cables
6. Gear train lock pin
7. Auxiliary switch B
8. Auxiliary switch A
9. Position indicator
10. Standard or self-centering shaft adapter*
11. Shaft adapter locking clip
12. Position indicator adapter
13. Mounting bracket

* Self-centering shaft adaptor shown

OPERATION
Two Position or Tri-state: A floating control signal controls the actuator. The actuator’s angle of rotation is proportional to the length of time the signal is applied. A 24 VAC control signal to wire 6 causes the actuator coupling to rotate clockwise.  A 24 VAC control signal to wire 7 causes the actuator coupling to rotate counterclockwise.

With no control voltage the actuator holds its current position.  In the event of a power failure, the actuator spring returns to the “0” position.

An improperly-tuned control loop will cause excessive repositioning that will shorten the life of the actuator.

Modulating Type: A continuous 4 to 20 mA or 0 to 10 VDC signal from a controller to wire 8  operates the actuator. The angle of rotation is proportional to the control signal. A 0 to 10 VDC position feedback output signal is available between wires 9 and wire 2(com)to monitor the position of the motor.

In the event of a power failure, or when the operating voltage is shut off, the actuator returns to the “0 ” position.

PLEASE CALL 1-800-253-2497 TO ORDER THESE ITEMS
Actuator Model Number Table
24 VAC Operating Voltage Torque Input Signal Cabling
Standard With Dual Auxiliary Switches & Potentiometer Dual Auxiliary Switches only Span/Offset Adjustable Dual Aux. Switches and Span/Offset Adjustable
ES62C2 ES62C2-S - - - 62 in-lb min.
(7 N-m)
Tri-state (floating) Standard Cable
ES75C2 ES75C2-S - - - 75 in-lb min.
(8.5 N-m)
Tri-state (floating) Plenum Cabling
ES142C2 ES142C2-S - - - 142 in-lb min.
(16 N-m)
Tri-state (floating) Plenum Cabling
ES62B2 - ES62B2-S ES62B2-ZS ES62B2-ZS-S 62 in-lb min.
(7 N-m)
0-10 VDC
0-20 mA
Plenum Cabling
ES75B2 - ES75B2-S ES75B2-ZS ES75B2-ZS-S 75 in-lb min.
(8.5 N-m)
0-10 VDC
0-20 mA
Plenum Cabling
ES142B2 - ES142B2-S ES142B2-ZS ES142B2-ZS-S 142 in-lb min.
(16 N-m)
0-10 VDC
0-20 mA
Plenum Cabling
ES142D2 - ES142D2-S - - 142 in-lb min.
(16 N-m)
4-20 mA Plenum Cabling

Specifications ES62C2(S) ES75C2(S) ES142C2 ES62B2(S)(ZS,S) ES75B2(S)(ZS,S) ES142B2(S)(ZS,S) ES142D22(S)
Power supply 24 VAC 24 VAC +20%-15%,50/60HZ 24 VAC 24 VAC +20%-15%,50/60HZ
Transformer sizing (class 2 power source required for UL, CSA)
Power consumption 5 VA running 8 VA running 5 VA running 9 VA running
Electrical connection  3 ft 18 GA appliance 3 ft 18 AWG plenum cable
Control signal "Y" - - - 0-10 VDC(max 35VDC), 0-20 mA(add 500 ohm, 1/4 W resistor across pins 2 & 8) 4-20 mA
Input resistance - - - >100 Kohm 100 Kohm (0.1 mA) 500 ohms
Operating range - - - 0-10 VDC, 0-20 mA(add 500 ohm, 1/4 W resistor across pins 2 & 8) 4-20 mA
Feedback signal - - - 0-10 VDC, ±1 mA max. for 95º
Overload protection electronic throughout 0º to 95º rotation
Potentiometer 0-1000 Ohms, max. 1 mA - - - -
Manual override 3 mm hex crank (shipped with actuator)
Angle of rotation mechanically limited to 95º
Minimum torque 62 in-lb min. 75 in-lb min 142 in-lb 62 in-lb min. 75 in-lb min 142 in-lb min. 142 in-lb min.
Direction of rotation Direction & Direction spring return, selectable when ordering (CW=clockwise Direction with power, counterclockwise by spring; CCW=reverse of CW)
Position indication  visual indicator, visual indicator, -5º to 90º (-5º is spring return position) 0 to 90º (0º is spring return position)
Shaft size 1/4" to 3/4" dia.
1/ 4" to 1/2"sq
3/8" to 1" dia.
1/4" to 3/4"sq
1/4" to 3/4" dia.
1/ 4" to 1/2"sq
3/8" to 1" dia.
1/4" to 3/4"sq
Minimum shaft length 3/4" (20 mm)
– Auxiliary switches (-S option) 24 to 250 VAC, 6 A res
12 to 30 VDC, 2A
Plenum 4A resistive, 24 VAC
Plenum 2A inductive, 24 VAC
24 to 250 VAC, 6 A res Plenum 4A resistive, 24 VAC
Plenum 2A inductive, 24 VAC
Switch range (-S option)
  – Switch A 0° to 90° with 5° intervals
  – Rec. range usage 0° to 45°
  – Factory setting
  – Switching hysteresis
Switch range (-S option)
  – Switch B 0° to 90° with 5° intervals
  – Rec. range usage 45° to 90°
  – Factory setting 85°
  – Switching hysteresis
Running time for 90º motor: 90 secs, constant
spring 15 secs typ. (60)
motor:120 secs, constant
spring: 25 sec Typ.
motor: 90 secs, constant
spring 15 secs typ.
motor:150 secs, constant
spring: 25 sec Typ.
motor: 90 secs, constant
spring 15 secs typ.
Humidity 95% RH noncondensing
Housing type NEMA type 1/IP40 according to EN60529; NEMA 4/4X housings available on request
Housing material Diecast aluminum
Ambient temperature -25°F to 130°F (-32°C to 55°C)
Storage temperature -25°F to 158°F (-32°C to 70°C)
Noise level   max. 20 dBA 20 dBA <45 dBA running
Servicing maintenance free
Agency ratings UL 873 or UL60730 listed, CE-UL certified to CSA C22.2 No. 24-93 (pending CE approval for plenum models)
CE conformity
Immunity
EMC: 89/336/EEC, Emissions: EN5081-1
EN61000-6-2 except EN50082-1 IEN50082-2
Quality standard ISO 9002
Weight 2.86 lbs (1.3 kg) 6 lbs (2.7 kg) - -

For assistance call 978-568-3400
pumps | valves | instrumentation | new products | contact clark | site/product directory | enewsletter | home