The two line X sixteen character alphanumeric display may be configured by the user to simultaneously display any two of the following: Flow Rate, Flow Total, Batch Status or Batch Count. The Batch Status mode may be programmed to count up or down, in either units of measure or percentage of batch. LEDs are used to indicate batching relay status.
The Series 2200 will measure a single batch, a preset number of batches or will batch continuously with a programmable time delay between batches. The "End of Batch" signal from one unit may be used to start another. Enabling the Automatic Overrun Compensation feature allows the 2200 to adjust the end of the batch based on the overrun of the previous batch.
The panel meter conforms to DIN Standard dimensions, 192 mm X 96 mm, for meter sizes and panel cutouts. The 2200 is also available in NEMA 4 and NEMA 4X wall mount versions.
The Series 2200 may be calibrated in the field. All flow sensors with a digital pulse, sine wave or analog sensors, including non-linear and logarithmic signals may be used. Up to twelve separate calibration points may be entered for linearization.
Programming is menu driven and all data is entered using five front panel mounted keys. A software lock allows the user to enter a password to prevent changing the totals, calibration or control settings. Programming flexibility is extended to the measurement units. The Series 2200 software contains nineteen rate of flow units and seven total flow units. There is also the provision for adding custom units for each. Also written into the software is a self-diagnostic program that assists the operator in troubleshooting any problems.
The 2200 also provides a standard pulse output to interface with other batch controllers or external data collection devices that accept a pulse or dry contact closure. The resolution of the TTL compatible signal may be programmed from the front keypad. All calibration information, units of measure, batch sizes and flow totals are stored in a non-volatile memory that does not require battery back-up for data storage.
A Model 2201 dual batch unit is available. This option allows two batch operations from a single unit. These can be volumetric batches from two flow streams using an optional input card, or time based. The dual batch version is equipped with four control relays. The 2200 is expandable with a long list of options to custom tailor the unit for individual requirements.
These options include:
- Second batch channel- converts the 2200 to a dual batch device.
- Display backlighting- with variable contrast for low light situations.
- Power supplies - 12 VDC, 12-36 VDC, 24 VAC, 115 VAC or 230 VAC.
- Mechanical counters - built-in, non-resettable seven digit mechanical counters.
- Control relays - C Form mechanical relays, two additional available, independently
programmed from the keypad by rate for alarms or pump control; or by
total for counting and proportioning.
- Analog output - isolated 4-20 mA, 0 to 5 Volt or 0 to 10 Volt outputs, programmed
from the keypad.
- Analog input - to accept inputs from other flow devices with analog outputs.
- RS232/485 port- allows two way serial communication with the 2200.
Power Supply Options:10-26 VAC/12-36 VDC (24 VAC/12-36 VDC option),
or 115/230 VAC, 50/60 Hz (115/230 VAC option),
or 10.6-16 VDC (12 VDC option)
Power Consumption: 8.5 Watts maximum
Display: two lines X 16 characters, alphanumeric, dot matrix LCD display with variable
contrast. Large 0.32" character height. STN (Super-Twisted Nematic) display type with
+/- 20 degree viewing angle, optional backlighting
Weight: 3 pounds maximum (panel mount with DIN draw mounting brackets), 9.2
pounds maximum wall mount
Operating Temperature: +32°F to +158°F (0°C to +70°C)
Storage Temperature: -40°F to +185°F (-40°C to +85°C)
Dimensions:
Panel Mount: 7.56"W x 3.78"H x 4.625"D
Wall Mount: 10.997"W x 9.5"H x 5.784"D
Sensor Input: digital pulse input
Input Impedance: 14 kOhms
Signal Amplitudes: 3 to 15 VDC (high) open or 0 to 1 VDC (low)
Frequency Input Range: 0 to 10 kHz
Sensor Calibration: 12 point linearization with 7 digit floating point K Factor and
frequency table entries
UNITS OF MEASURE:
Flow rate: 19 standard, 1 custom programmable, custom flow rate unit: 7 character
label 7 digit floating point conversion from gallons/minute to custom unit
Flow total: 7 standard, 1 custom programmable, custom flow total unit: 4 character
label 7 digit floating point conversion from gallons to custom unit
Totalizer:
Range: 0 to 1,000,000,000 (i.e. 0 to 1,000,000,000 gallons, 0 to 1,000,000,000
liters, etc.)
Data Update Rate: adjustable 0.5 seconds to 5.0 seconds in 0.5 second increments,
adjustable averaging function for smoothing erratic flow rates
Pulse Output: Open collector transistor pulse in any standard or custom flow total units,
adjustable 25 mS to 5.0 second pulse output width in 25 mS increments, Maximum
sinking current: 300 mA @ 36 VDC
Batch Relay Output: SPDT contacts, 6.0 amps @ 250 VAC or 30 VDC maximum resistive
load, user configured as batch relay, pre-warn, or overrun relay, coil energizes at
"start" and de-energizes at "stop" or end of batch function
Relay Option: 2 optional relays-single batch unit only, SPDT contacts, 6.0 amps @ 250
VAC or 30 VDC maximum resistive load, user configurable as totalizer, high rate alarm,
or low rate alarm, adjustable 0 to 120 second delay (in 0.5 second increments) until
activation for alarm functions, 0 to 50% (of set point) hysteresis for alarm functions
Totalizer Option: Two 7 digit, non-resettable electromechanical counters, user
configurable output in any standard or flow total units or number of batches
|
|
|