Clark Solutions
One Series, 2-Wire Electronic Pressure & Temperature Switches
E F.S. Ranges 5 to 4500 PSI, -50 to 450°F, 100% F.S. Deadband & Set Point Adjustment

(Page 4 of 6)
Page 1 2 3 4 5 6

SPECIFICATIONS

Power input: 12-30 VDC or 90-130 VAC or VDC (derived from PLC/DCS discrete
      input or through a suitable series load). Refer to Installation and
      Maintenance Sheet IM2W for additional information
Accuracy: 0.5% of full range span, under nominal conditions
Repeatability: 0.1% of full range span
Ambient operating temperature range: -40 to 85°C; -20 to 70°C
      (Full display visibility)
Temperature drift: 300 ppm/°C
Switch response time: “Change-of-output” response within 50 mS (for detection
      of full step change and change of output state, delay feature off)
Display response time: 400 mS
Response time filtering (Delay): Software-configurable between 250 mS and 2
      seconds in 2x increments
Diagnostics (IAW®): Open or shorted sensor; plugged port; power supply out
      of range; over and under-range conditions; microprocessor faults/failure;
      keypad short; switch fault
Output states: Field selectable for 2-state or 3-state operation.
      For 3-state operation: Output will remain in closed state during normal
            (“inside threshold”) operation; change to open state to indicate a
            fault/failure; and change between closed and open (pulse) state on a
            25 mS or 100 mS cycle (user defined) during “at and outside threshold”
            conditions
      For 2-state operation: Output will remain in one state (open or close) during
            normal (“inside threshold”) operation; change to the opposite state for
            “at and outside threshold” conditions. Unit must be configured as
            normally closed (Open rise or Open fall) in order to achieve “fail-safe”
            condition so that a diagnostic or other failure will produce an open
            output state.
Control modes: Field configurable for change of state above or below set point
      value. Software configurable for automatic or manual reset
Switch output: SPST solid state device, to interface with 12-30 VDC or 90-130
      VAC input from PLC, DCS or relay. May be wired for either sourcing or
      sinking operation
Electrical characteristics: Model 2W2D- Switch open:12-30 VDC @750 µA
      maximum; Switch closed: 4.7VDC @40mA, maximum.
Model 2W3A- Switch open: 90-130 VAC or VDC @ 1mA maximum, switch closed:
      13 VAC or VDC @ 100 mA, maximum
Enclosure: Designed to meet NEMA 4X/IP66, epoxy-coated aluminum
Faceplate: UV-resistant Lexan® (polycarbonate) with 2-button membrane
      switch and overlay
Wiring terminations: Terminal block with 3 screw connections (2 for switch
      output and one to ground chassis). Accepts 14-22 AWG wire.
Conduit: 1/2” NPT (female)
Display: Local 4 digit x 0.5” LCD
      I Am Working (IAW®) status arrows
      Process Variable
      Units of measure
      Switch status
      Latch status
      Set point value
      Deadband value
      Min/Max values
      Fault codes
Set point & deadband: User-configured, 100% adjustable over entire sensor
      range
Pressure sensor: 316 stainless steel, welded diaphragm, 1/2” NPT (female)
      connection, micro-machined piezoresistive silicon element
Media temperature: -40 to 257°F (-40 to 125°C) Pressure Sensors
Temperature sensors: 304 stainless steel, 100 ohm 4-wire RTD, 0.25” OD epoxy
      filled sheath (Local and Remote models), powder packed sheath (High-
      temperature models)
Media range: -50 to 1000°F (-45 to 538°C) Temperature Sensors
EMI/RFI: Compliance to CE EMC requirements EN5011:1998:A1,
      EN61000-6-2:1999
Emission: EN55011 class A; Radiated emissions
Immunity: EN61000-4-2 Immunity to Electrostatic Discharge
      EN61000-4-3 Immunity to Continuous Radiated Disturbances
      EN61000-4-4 Immunity to Electrical Fast Transients
      EN61000-4-5 Immunity to Surges
      EN61000-4-6 Immunity to Continuous Conducted Disturbances
      EN61000-4-8 Immunity to Power Frequency Magnetic Field
Memory: Programming and data protected by Non-Volatile EEPROM
Effective transmission distance: 2,000 feet at rated voltage

Lexan® is a registered trademark of General Electric Co.
IAW® is a registered trademark of United Electric Controls Co
.

Configuration Selection Guide Power and Switch Options
Input Type Input Voltage Range Max. Switch Output Capacity Model Number
24 VDC PLC/DCS/PC 12-30 VDC 30 VDC@ 40 mA 2W2D00
24 VDC Relay or Solenoid Coil 12-30 VDC 30 VDC@ 40 mA 2W2D00
115 VAC PLC/DCS/PC 90-130 VAC 130 VDC@ 100 mA 2W3A00
115 VAC Relay or Solenoid Coil 90-130 VAC 130 VDC@ 100 mA 2W3A00
125 VAC PLC/DCS/PC 90-130 VAC 130 VDC@ 100 mA 2W3A00
115 VAC Relay or Solenoid Coil 90-130 VAC 130 VDC@ 100 mA 2W3A00
Page 1 2 3 4 5 6

      For assistance call 978-568-3400