DESCRIPTION
Clark offers a complete line of Butterfly valves for both commercial and industrial applications. The valves are designed for hot and chilled water, as well as steam applications up to 10 PSI saturated steam inlet. The valves can be used for on/off or throttling control, isolation, flow balance, mixing or diversion.
Valves are available in full-lugged or wafer mounting style. All bodies meet ANSI 150 pressure ratings for hydrostatic requirements. The valves are compatible with ANSI 125/150 flanges. Standard valves 2"-12" are bidirectional with a bubble-tight shut-off pressure rating of up to 250 PSI dead end service. Valves 14"-20" are also bidirectional with a bubble-tight shut-off standard pressure rating of 50 PSI. Rating to 150 PSI is available with non-undercut (NU) discs.
A selection of commercial grade actuators and industrial grade NEMA 4/4X actuators are available
VALVE & ACTUATOR SELECTION
(UNITS ARE SUPPLIED FULLY ASSEMBLED & TESTED)
1) Review our Motor Actuated Valve Application Guide and select the
valve type, size & materials. Refer to Clark bulletins on Ball
valves or Globe valves if these valve types are better suited to
the application.
2) Review valve C v and close-off rating chart (Tables A & B) and select
base valve model and actuator model.
3) Review Valve and actuator dimensions.
4) Review selected actuator spec. sheet and determine specific actuator
model number.
5) Assemble final model number using model number guidelines under
"Ordering Information".
|
|
| Table A |
Commercial Actuator Selection Chart for valve sizes 2" to 6" |
| Valve Size |
Cv |
Base Valve Model |
Actuator Model Number/Maximum Close-off- PSI |
| Two Position |
Modulating |
Two-way Differential Pressure (PSI) |
Three-way Differential Pressure (PSI) |
| @90º |
@70º |
Two-Way |
Three-way |
50 |
100 |
150** |
50 |
100 |
150** |
| 2" |
60 |
52 |
RS2A-2 |
RS3A-2 |
ES142 |
ES142 |
ES142 |
ES142 |
ES142* |
ES142* |
| EN177 |
EN177 |
EN177 |
EN177 |
EN177 |
EN177 |
| 2 1/2" |
151 |
107 |
RS2A-2.5 |
RS3A-2.5 |
ES142 |
ES142* |
ES142* |
ES142* |
ES142* |
EN310* |
| EN177 |
EN177 |
EN310 |
EN310 |
EN310 |
| 3" |
262 |
175 |
RS2A-3 |
RS3A-3 |
ES142* |
ES142* |
ES142 |
ES142* |
ES142* |
EN310* |
| EN310 |
EN310 |
EN310 |
EN310 |
EN310 |
| 4" |
647 |
453 |
RS2A-4 |
RS3A-4 |
ES142* |
EN310* |
EN310* |
ES142* |
EN310* |
EN310* |
| EN310 |
EN310 |
| 5" |
1141 |
832 |
RS2A-5 |
RS3A-5 |
EN310* |
EN310* |
EN310* |
EN310* |
- |
- |
| 6" |
1580 |
1160 |
RS2A-6 |
RS3A-6 |
EN310* |
- |
- |
EN310* |
- |
- |
| * Requires two actuators |
| ** Call for close-offs greater than 150 PSI |
| Table B |
Industrial Actuator Selection Chart for valve sizes 2” to 20” |
| |
CV |
|
Actuator Model/Maximum Close-off- PSI |
| Valve Size |
Two Position |
Modulating |
Valve Model |
Two-Way Differential Pressure (PSI) |
Three-way Differential Pressure (PSI) |
| @90° |
@70° |
Two-way |
Three-way |
50 |
100 |
150* |
50 |
100 |
150* |
| 2” |
60 |
52 |
RS2A-2 |
RS3A-2 |
RE1.5 |
RE1.5 |
RE1.5 |
RE1.5 |
RE3 |
RE3 |
| 2 1/2” |
151 |
107 |
RS2A-2.5 |
RS3A-2.5 |
RE3 |
RE3 |
RE3 |
RE3 |
RE3 |
RE6 |
| 3” |
262 |
175 |
RS2A-3 |
RS3A-3 |
RE3 |
RE3 |
RE3 |
RE3 |
RE6 |
RE6 |
| 4” |
647 |
453 |
RS2A-4 |
RS3A-4 |
RE3 |
RE6 |
RE6 |
RE3 |
RE6 |
RE6 |
| 5” |
1141 |
832 |
RS2A-5 |
RS3A-5 |
RE6 |
RE6 |
RE10 |
RE6 |
RE10 |
- RE10 |
| 6” |
1580 |
1160 |
RS2A-6 |
RS3A-6 |
RE6 |
RE10 |
RE10 |
RE6 |
RE15 |
RE15 |
| 8” |
2892 |
2524 |
RS2A-8 |
RS3A-8 |
RE15 |
RE20 |
RE20 |
RE15 |
RE25 |
RE30 |
| 10” |
4593 |
3470 |
RS2A-10 |
RS3A-10 |
RE20 |
RE15T |
RE15T |
RE20 |
RE20T |
RE20T |
| 12” |
6682 |
5600 |
RS2A-12 |
RS3A-12 |
RE30 |
RE20T |
RE20T |
RE20T |
RE25T |
RE25T |
| 14” |
10000 |
7400 |
RS2A-14 |
RS3A-14 |
RE30 |
RE25T |
RE25T |
RE20T |
call |
call |
| 16” |
13000 |
9600 |
RS2A-16 |
RS3A-16 |
RE20T |
RE30T |
call |
RE25T |
call |
call |
| 18” |
18000 |
96000 |
RS2A-18 |
RS3A-18 |
RE25T |
call |
call |
call |
call |
call |
| 20” |
22000 |
12000 |
RS2A-20 |
RS3A-20 |
RE30T |
call |
call |
call |
call |
call |
-ratings based on 10ft/sec max. fluid velocity
*call for close-offs greater than 150 PSI

| Table C |
Valve Dimensions (inches) |
| |
|
|
|
|
|
Mounting Flange Drilling |
|
|
|
|
Lug Bolt Data |
| |
|
|
|
|
Threads |
| Valve Size |
A |
B |
C |
D |
E |
F |
BC |
#Holes |
Hole Dia. |
G |
H |
Q* |
Key |
BC |
#Holes |
UNC-2B |
| 2” |
2.06 |
4.13 |
5.32 |
1.69 |
4.00 |
1.25 |
3.25 |
4 |
0.44 |
0.56 |
0.38 |
1.38 |
n/a |
4.75 |
4 |
5/8-11 |
| 2 1/2” |
2.56 |
4.63 |
5.94 |
1.81 |
4.00 |
1.25 |
3.25 |
4 |
0.44 |
0.56 |
0.38 |
2.00 |
n/a |
5.50 |
4 |
5/8-11 |
| 3” |
3.06 |
5.19 |
6.31 |
1.81 |
4.00 |
1.25 |
3.25 |
4 |
0.44 |
0.56 |
0.38 |
2.63 |
n/a |
6.00 |
4 |
5/8-11 |
| 4” |
4.06 |
6.38 |
7.13 |
2.06 |
4.00 |
1.25 |
3.25 |
4 |
0.44 |
0.63 |
0.44 |
3.69 |
n/a |
7.50 |
8 |
5/8-11 |
| 5” |
5.06 |
7.38 |
7.69 |
2.25 |
4.00 |
1.25 |
3.25 |
4 |
0.44 |
0.75 |
0.50 |
4.75 |
n/a |
8.50 |
8 |
3/4-10 |
| 6” |
5.81 |
8.50 |
8.31 |
2.25 |
4.00 |
1.25 |
3.25 |
4 |
0.44 |
0.75 |
0.50 |
5.56 |
n/a |
9.50 |
8 |
3/4-10 |
| 8” |
7.81 |
10.69 |
9.50 |
2.38 |
6.00 |
1.25 |
5.00 |
4 |
0.56 |
0.88 |
0.63 |
7.75 |
n/a |
11.75 |
8 |
3/4-10 |
| 10” |
9.81 |
13.00 |
10.88 |
2.69 |
6.00 |
2.00 |
5.00 |
4 |
0.56 |
1.13 |
n/a |
9.75 |
1/4x1/4 |
14.25 |
12 |
7/8-9 |
| 12” |
11.81 |
14.38 |
11.25 |
3.13 |
6.00 |
2.00 |
5.00 |
4 |
0.56 |
1.13 |
n/a |
11.75 |
1/4x1/4 |
17.00 |
12 |
7/8-9 |
| 14” |
13.25 |
16.75 |
12.00 |
3.00 |
6.00 |
3.00 |
5.00 |
4 |
0.56 |
1.38 |
n/a |
13.13 |
5/16/5/16 |
18.75 |
12 |
1-8 |
| 16” |
15.25 |
19.00 |
12.95 |
4.00 |
6.00 |
3.00 |
5.00 |
4 |
0.56 |
1.63 |
n/a |
15.00 |
3/8x3/8 |
21.25 |
16 |
1-8 |
| 18” |
17.25 |
21.38 |
14.50 |
4.25 |
8.00 |
4.25 |
6.50 |
4 |
0.81 |
1.88 |
n/a |
16.88 |
1/2x3/8 |
22.75 |
16 |
1 1/8-7 |
| 20” |
19.25 |
23.50 |
15.88 |
5.00 |
8.00 |
4.25 |
6.50 |
4 |
0.81 |
1.88 |
n/a |
18.75 |
1/2x3/8 |
25.00 |
20 |
1 1/8-7 |
Standard 2 - 12 valves have fixed resilient seats, 14 and above have removable seats
* Q dimension is the minimum allowable pipe or flange inside diameter at the centered body face to protect the disc sealing
edge against damage when opening the valve.
| Two-Way Valve, 2” through 6” |
| With Commercial Actuators |
| Size |
Model |
Dimensions |
| A |
| 2” |
RS2A-2 |
9.1 |
| 2 12” |
RS2A-2.5 |
9.6 |
| 3” |
RS2A-3 |
10.0 |
| 4” |
RS2A-4 |
10.8 |
| 5” |
RS2A-5 |
11.4 |
| 6” |
RS2A-6 |
12.0 |
| Actuator Dimensions |
| Actuator |
Dimensions (inches) |
| B* |
C |
D |
E‡ |
| Spring Return |
| ES142 |
2.9 |
8.8 |
2.3 |
4.0 |
| Non-Spring Return |
| EN177 |
2.5 |
6.4 |
1.7 |
3.2 |
| EN310 |
2.9 |
8.8 |
2.3 |
4.0 |
E dimension is the actuator width
|
|
 |
| Two-Way Valve, 2” through 14” |
| With Industrial RE Series Actuators |
| Size |
Model |
Dimensions |
| A |
| 2” |
RS2A-2 |
8.4 |
| 2 12” |
RS2A-2.5 |
9.0 |
| 3” |
RS2A-3 |
9.3 |
| 4” |
RS2A-4 |
10.2 |
| 5” |
RS2A-5 |
10.7 |
| 6” |
RS2A-6 |
11.3 |
| 8” |
RS2A-8 |
12.5 |
| 10” |
RS2A-10 |
13.9 |
| 12” |
RS2A-12 |
14.3 |
| 14” |
RS2A-14 |
16.0 |
| RE Series NEMA 4/4x Actuator Dimensions |
| Actuator |
Dimensions (inches) |
| B |
C |
D |
E |
F |
| Non-Spring Return |
| RE1.5-RE6 |
9.93 |
5.15 |
3.48 |
7.42 |
1/2” NPT |
| RE10-RE30 |
11.65 |
6.07 |
4.40 |
9.75 |
3/4” NPT |
-Valves are sometimes directly mounted to actuator (no bracket)
-Call valve for sizes 16 and larger
|
|
 |
| Three-Way Valve, 2" through 6" With Commercial Actuators |
| Size |
Valve Model |
Actuator Model |
Dimensions (inches) |
| A |
B |
C |
D |
E |
F |
G |
| 2" |
RS3A-2 |
ES142/EN177 |
4.50 |
1.69 |
1.38 |
3.36 |
5.31 |
9.01 |
3.50 |
| 2 1/2" |
RS3A-2.5 |
ES142*/EN310 |
5.00 |
1.81 |
2.00 |
3.36 |
5.94 |
9.64 |
3.50 |
| 3" |
RS3A-3 |
ES142*/EN310 |
5.50 |
1.81 |
2.63 |
3.36 |
6.31 |
10.01 |
3.50 |
| 4" |
RS3A-4 |
ES142*/EN310 |
6.50 |
2.06 |
3.69 |
3.36 |
7.13 |
10.83 |
3.60 |
| 5" |
RS3A-5 |
EN310* |
7.50 |
2.25 |
4.75 |
4.77 |
7.69 |
11.39 |
2.90 |
| 6" |
RS3A-6 |
EN310* |
8.00 |
2.25 |
5.56 |
4.77 |
8.31 |
11.86 |
2.90 |
| Three-Way Valve, 2" through 12" With Industrial RE Series Actuators |
| Size |
Valve Model |
Actuator Model |
Dimensions (inches) |
| A |
B |
C |
D |
E |
F |
G |
| 2" |
RS2A-2 |
RE1.5 |
4.50 |
1.69 |
1.39 |
3.36 |
5.31 |
7.31 |
9.26 |
| 2 1/2" |
RS2A-2.5 |
RE3 |
5.00 |
1.81 |
2.00 |
3.36 |
5.94 |
7.94 |
9.26 |
| 3" |
RS2A-3 |
RE3 |
5.50 |
1.81 |
2.63 |
3.36 |
6.31 |
8.31 |
9.26 |
| 4" |
RS2A-4 |
RE3 |
6.50 |
2.06 |
3.69 |
3.36 |
7.13 |
9.13 |
9.26 |
| 5" |
RS2A-5 |
RE6 |
7.50 |
2.25 |
4.75 |
4.77 |
7.69 |
9.69 |
9.26 |
| 6" |
RS2A-6 |
RE6 |
8.00 |
2.25 |
5.56 |
4.77 |
8.31 |
10.13 |
9.26 |
| 8" |
RS2A-8 |
RE15 |
9.00 |
2.38 |
7.75 |
5.47 |
9.50 |
12.50 |
11.65 |
| 10" |
RS2A-10 |
RE20 |
11.00 |
2.69 |
9.75 |
6.54 |
10.88 |
13.88 |
11.65 |
| 12" |
RS2A-12 |
RE30 |
12.00 |
3.13 |
11.75 |
6.54 |
12.25 |
15.25 |
11.65 |
*Requires two actuators
-Call for valve sizes 16 and greater
|
 |
|
 |
| PLEASE CALL 1-800-253-2497 TO ORDER THESE ITEMS |
| Valve Model Number |
| A Base Model |
B Optional Materials Select as many as apply |
C Mounting Style |
D Three-Way Mounting Arrangement |
| |
- = none |
|
|
| See Tables A & B Standard Materials are : Cast Iron Body Aluminum Bronze Disc Stainless Steel Stem EPDM Seat |
IB=Ductile Iron Body SB=Cast Steel Body AB=Aluminum Body ID=Ductile Iron Disc(Phosphate or Nylon 11 Coated) SD= Stainless Steel Disc CS=Carbon Steel Disc BS= BUNA-N Seat |
L=Lugged type W=Wafer Type |
1= 1
2= 2
3= 3
4= 4
5= 5
6= 6 |
| |
VS= Viton GF Seat |
|
|
For assistance call 978-568-3400
|
|