UTLFB Series Liquid Ultrasonic Flow Transmitters

Loop Powered 4-20 mA Output, Flows to 400 GPM, 3/4" to 3" Pipe, Brass

DESCRIPTION

Clark UTLFB Ultrasonic Flowmeters are ideal for measurement of flow rates of acoustically conductive liquids including most clean liquids and many liquids with entrained solids.

Main advantages include excellent long term stability, no pressure drop, broad fluid compatibility, high accuracy and low cost. Model UTLFB has no moving parts.

At the heart of Series UTLFB is a proprietary mixed signal ASIC which allows sophisticated timing, control and transducer drive circuitry to be combined on a single integrated circuit. The ASIC uses a special algorithm that is an improvement upon the standard single-path measurement technique. Using the "sing around" method, the ultrasonic transducer alternates between transmitting and receiving to measure differences in flight time between upstream and downstream transmissions. A sound pulse is transmitted from an upstream transducer towards a downstream transducer like a traditional time-of-flight measurement. However, the received sound pulse then triggers a second downstream transmission that then triggers a third and so on for a specific number of cycles. Then, this process is repeated in the upstream direction.

Because it takes an average flight time over multiple cycles to compute the difference in flight times, the approach yields a significant improvement in timing accuracy when compared with the time-of -flight difference of a single sound pulse in each direction. This algorithm, combined with the pico-second timing resolution of the ASIC, provides the precise time measurement capability necessary for compact, small diameter ultrasonic meters.

The output of model UTLF is unaffected by changes in fluid temperature, density and viscosity as the flow calculation is independent of the speed of sound.

Wetted materials include ULTEM® encapsulated ultrasonic transducers with a choice of elastomer seals and brass body material.

SPECIFICATIONS

GENERAL
Flow Range: Bi-directional, field selectable per "Standard Models" table
Accuracy: ±1.0% of reading
Operating Temperature: -40 to 150°F
Response Time: User Selectable, 2 or 10 seconds
Viscosity Range: 0.2 to 150 mPas (0.2 to 150 cSt)
Liquid Density: 490 to 1200 kg/m3 (30.6 to 74.9 lb/cu.ft.)
Max. Working Pressure: 200 PSI
Pipe Sizes: 3/4", 1", 1 1/2", 2", 3"
Pipe Connections:
Sizes 3/4" to 2"- Female NPT, BSP
Size 3": ASME 150 or DIN 16 Flange
Electrical Enclosure: Integral to Body casting with gasketed cover and M16 x 1.5 strain 
	relief fitting for 5-8 mm outside diameter cable
Electrical Connections: Screw terminal connections on PC board
Enclosure Rating NEMA 4 (IP 65)
Power: 15 to 32 VDC

WETTED MATERIALSUltrasonic Transducers: ULTEM® Encapsulated
Seals: Buna-N, Neoprene, FKM, or other
Body Material: Brass (UNS C83600)

OUTPUT
Analog: 2-wire, 4-20 mA output, 600 ohm max ;
Output is 4 mA from zero to min. flow (see Standard Model table)
Error Detection: An optically isolated 25 mA (max. 48V no load voltage) sink output is 
	activated under certain detectable fault conditions, such as transducer failure or overly 
	noisy output due to flow stream anomalies, as might be seen due to excessive bubble entrainment.
Direction of Flow: Optional output to indicate direction of flow is available. Activation or deactivation 
	of an optically isolated 25 mA (max. 48V no load voltage) sink output indicates flow direction. 
	Error detection is not available when this option is ordered.
	

Meter Size A B C D E
Inches mm Inches mm Inches mm Inches mm Inches mm
3/4" & 1" 9.0 229 1.62 41.1 2.0 50.8 6.4 163 2.4 61
1-1/2" & 2" 9.7 246 2.75 69.9 2.7 68.6 6.4 163 2.4 61
Meter Size A B C D E
Inches mm Inches mm Inches mm Inches mm Inches mm
ASME 150 11 - ∅ 7.5 - 3.3 - 6.4 - 2.4 -
DIN 16 - 280 - 190 - 84 - 163 - 61
STANDARD MODELS
Model Pipe Size/Thread Size *Field Selectable F.S. Ranges (GPM) *Field Selectable F.S. Ranges (LPM)
Min. Max. Min. Max.
UTLFB34 3/4" NPT or BSP 0.18 15 0.72 60
0.31 25 1.20 100
UTLFB10 1.0" NPT or BSP 0.38 30 1.38 115
0.63 50 2.40 200
UTLFB15 1.50" NPT or BSP 0.50 40 1.80 150
1.00 80 3.60 300
UTLFB20 2.0" NPT or BSP 0.75 60 2.70 225
1.88 150 6.90 575
UTLFB30 3" ASME Class 150 Flange
80 mm DIN Class 150 Flange
2.48 200 9.00 750
4.96 400 18.00 1500

*Other F.S. ranges can be specified

ORDERING INFORMATION ORDER NUMBER (ABCD) Example: UTLFB10NPTGB
A=Model B=Pipe Thread C=Units of Measure D=Transducer Seal
UTLFB34 3/4" to 2" G= Gallons Per Minute (U.S.) B= Buna-N
UTLFB10 NPT= Female NPT L= Liters Per Minute N= Neoprene®
UTLFB15 BSP=Female British Standard Pipe (G)   V= FKM
UTLFB20 3"  
UTLFB30 ASME= ASME Class 150 Flange
  DIN= DIN Class 16 Flange
 
Options
DF= Direction of flow output option
*For non-listed ranges specify model followed by full span value
Example: UTLFB15-50G = 50 GPM at 20 mA or UTLFB15-200L=200LPM @ 20 mA