Valves >> General Purpose Solenoid Valve >> General Industry Solenoid Valves
CLARK SOLUTIONS

Technical Bulletin, General Industry Solenoid Valves


Installation and Troubleshooting.

MODELS COVERED IN THIS BULLETIN: 1314, 1323, 1325, 1327, 1335, 1342, 1365,1390, 1393, 2026, 2036

ELECTRICAL INSTALLATION
All the coils are for continuous use - permanent or high frequency operation.

Check that the coil supplied with the valve has the correct voltage and current required. If not, replace it with the adequate coil without changing the valve.  The allowed voltage variation that does not affect the performance of the valve is -15% to +10% of the nominal voltage for AC and -10% to +10% for DC.  Except for valve series 1314, the models are generally supplied with DIN 43650 Connection (ISO 4400) and encapsulated coils.

MECHANICAL INSTALLATION
• Verify that the working conditions are
   within the range of differential
   pressure and temperature indicated
   on the nameplate of the 
valve.
• Place a strainer with adequate
   capacity and a mesh smaller than
   100 µ immediately upstream from the
   valve.
• The most favorable mounting position
   is on a horizontal pipeline with the coil
   upright.
• Pipelines upstream from the valve
   must be carefully and exhaustively
   cleaned even before the strainer, by
   means of purges with compressed air
   or any other system that guarantees
   the disposal of solid elements as well
   as welding bits, mud, dirt, etc.,
   especially with new pipelines.
• Follow the arrow that indicates the
   flow direction in the valve’s body. The
   input pressure must always be equal
   or greater than the output pressure.
INSTRUCTIONS FOR THE ELECTRICAL CONNECTION WITH STRAIN RELIEF
1. Unscrew the screw (8) to reach the block (3), where the
    terminals are. The system is designed to use armored
    cables with 3 “PG9” conductors. Carry out Neutral - Live
    - Ground connections.

2. Insert the terminal block into the cover (4) according to
    the desired entrance angle, in any of the four possible
    positions: Left, Right, Above, Below.

3. Insert the coil blades into the connector. Fasten it with
    the screw (8). 4.Finally but very important, tighten the
    strain relief (7) to make sure that it is hermetic.
    Otherwise, moisture may enter and cause a short-circuit
    between the terminals.

INSTRUCTIONS FOR THE COVER WITH AN OPENING FOR 1/2 NPT CONDUIT
1. Follow instructions 1, 2 and 3 for strain relief connector.
2. It is important to be sure that the interconnection is
    hermetic, so we recommend the use of a sealant or
    gasketing tape over the threads.

COIL FIXING
The nut (9) that fixes the coil to the core-tube must be 5 Nm / 0.5 kpm / 3.75 lbf, to prevent the coil from turning round.  Avoid unnecessary tension that may damage the core-tube due to excess of torsion.

TROUBLE SHOOTING PROBLEMS
Most of the failures that occur when starting a new installation are the result of lack of cleanness in the pipelines between the filter and the valve, due to left-overs of packaging, Teflon, welding residue, dirt, etc.. However, in spite of having made a good choice, a good installation and the adequate maintenance, some contingent factors may occur after the installation and disturb a suitable operation. The following page shows the most common failures with their possible causes and solution.

1 Coil
2 Gasket
2a Optional gasket with energized coil indicator light.
3 Electric terminals block. Maximum wire size AWG14
   (1.6 mm.)
4 Cover with opening for armored cable. Strain relief
   “PG9”, for cable O.D. from 6 to 8 mm. Cover with
   indicator light upon request.
4a Cover with opening for conduit. 1&Mac218; NPT Connection.
     (Part No 3189-2). Cover with indicator light upon
     request.
5 Strain relief gasket.
6 Washer.
7 Strain relief.
8 Fixing screw.
9 Coil fixing nut.
PROBLEM POSSIBLE CAUSES SOLUTIONS
 1. Valves do not open when energized (NC) or when de-energized (NO). For direct acting valves

1. Voltage less than 15% of the nominal voltage.

1. Check the coil voltage, which must not be less than 85% of the indicated nominal voltage. If this is the case, adjust the source to the adequate value.

2. Too high a differential pressure for that model.

2. Reduce pressure to the maximum shown on the valve nameplate or change it for a more adequate one.

3. Burnt coil (with the circuit open).

3. See Burnt Coils (Problem 3).

4. Plunger jammed with solids.

4. Clean the plunger’s core tube and the valve. If the system lacks an adequate strainer before the valve, the problem will persist.

5. Damaged plunger.

5. Replace the damaged part. Damage may be caused by fluid abrasive elements or high operation frequency over a long period of time and exceeding the part’s life.

For pilot operated valves
The same as above plus:

6. Differential pressure too low.

6. This factor should be considered when choosing a valve. It may occur due to over-sizing or reduction of differential pressure. If differential pressure cannot be increased by increasing the flow, the valve must be changed for an adequate one.

7. Jammed pilot piston.

7. Check that solids have not affected the piston’s movement. After cleaning, check that it is not damaged. A strainer must be placed upstream from the valve to eliminate the problem.

8. Damaged pilot piston, pilot piston rings or diaphragm.

8. Change damaged parts. Check that the cause is not dirt. Also see solution #1.

9. Pilot orifice blocked.

9. Clean the orifice, if the orifice is damaged consult Clark. Also see solution #1.

10. Pilot gasket damaged or misaligned.

10. This is caused by poor assembly. Change the damaged part and assemble the valve correctly. The O-ring must be correctly fitted.

11. Excessive viscosity. 11. Fluids with vicosities exceeding 60 cSt cannot be used with pilot operated valves
2. The valve remains open For direct acting valves
1. The coil was not de-energized (NC valve) or energized (NO valve). 1. Check the control circuits.

2. Plunger jammed with solids.

2. Clean the plunger’s core tube and the valve. If the system lacks an adequate strainer before the valve, the problem will persist.

For pilot assisted valves
The same as above plus:

3. The pilot orifice does not close.

3. Check that the plunger is not jammed or the seats damaged. In the first case, clean it, in the second case, change it. If the orifice seat is damaged, consult Clark.

4. Compensation orifice blocked.

4. Clean the orifice, if the orifice is damaged consult Clark.

5. Jammed pilot piston.

5. Check that solids have not affected the piston’s movement. After cleaning, check that it is not damaged. A strainer must be placed upstream from the valve to eliminate the problem.

6. Pilot piston, Pilot piston rings or diaphragm damaged. 6. Change the damaged parts. Check that the cause is not dirt.
7. Excessive viscosity. 7. Fluids with viscosities exceeding 60 cSt cannot be used
3. The coil gives off a burning smell after working for a short period or it burns up frequently. 1. Excessive voltage.

1. The voltage must not exceed 10% of the nominal voltage, and only for brief periods. Correct the voltage.

2. Only for AC: Too high a pressure that does not allow the pilot to open, therefore, only inrush current is present, which doubles the holding current.

2. Adjust the maximum working pressure to the maximum shown on the nameplate. If pressure is within the parameters, check that voltage is not less than 85% of the nominal voltage.

3. The coil’s nominal voltage is less than the source’s or does not correspond to its cycling.

3. Check that the voltage and current type is as indicated on the coil.

4. Excessive fluid or ambient temperature.

4. The fluid, atmosphere and power of the coil determine the internal temperature. As a general rule, the fluid temperature + ambient temperature must not exceed 210ºC. The fluid temperature cannot be above 180ºC. When handling hot fluids and the ambient exceeds 30ºC, it is advisable to fit the valve in the most ventilated area.

5. Moisture entering the interior of the coil

5. Check that DIN coils’ strain relief is tight and the armored cable corresponds to the connector PG size. For series 1314, check that the housing and connection are closed. See mounting recommendations.

6. Lack of part of the electromagnetic package when it is not integrated to the coil.

6. Replace the missing parts because they are part of the magnetic circuits and their absence results in an increase of the intensity which reduces the force of the magnetic attraction.

7. It is energized outside the valve (AC only). 7. Do not energize the coil if it is not fitted to the valve.
4. The coil vibrates when energized. 1. Insufficient voltage. 1. Adjust the voltage within the permitted parameters.
2. Dirty fixed core and plunger surfaces, they have scales. 2. Clean the surfaces. If scales remain there, change the components.
5. Fluid leakage when closed. 1. Main or pilot seat damaged or dirty. 1. Clean or change seats. If the orifice seats are damaged, consult Clark.
6. It operates slowly or fails. 1. Compensation or pilot orifice partially blocked. 1. In case of dirt, clean the orifices. In case of damage, consult Clark.
2. Excessive fluid viscosity. 2. The fluid’s viscosity must not exceed 60 cSt.
3. Temporary excess or lack of differential pressure. 3. Check that both differential and opening pressure differential are within the limits indicated in the valve nameplate.